Plan Review Notes
Plan Review Notes For Permit 21121052
Permit Number 21121052
Review Stop G
Sequence Number 2
Notes
Date Text
2022-03-15 13:20:182ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21121052
 3/15/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS RROM THE
 1SRT REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 2) FAILED. FG2.1 GAS RISER: B) SHOW THE TOTAL DEVELOPED
 LENGTH OF THE SYSTEM FROM THE METER TO THE MOST REMOTE
 APPLIANCE OUTLET- SEC. 402.4.1 FBC FG. NOT PROVIDED.
  
 4) FAILED. FG1.1 & FG1.2: AN AUTOMATIC GAS SHUTOFF
 VALVE WITH MANUAL RESET IS REQUIRED TO BE CONNECTED TO
 THE HOOD FIRE SUPPRESSION SYSTEM PER SEC. 10.4.1 NFPA
 96. THE VALVE DOES NOT APPEAR TO BE IN AN ACCESSIBLE
 LOCATION AS REQUIRED. PLEASE CORRECT THE PLAN AND
 PROVIDE THE VALVE SPECIFICATIONS. VALVE LOCATION NOT
 SHOWN ON RISER
  
 6) FAILED. FG1.1: INDICATE THE TYPE OF CONCENTRIC DUCT
 ON THE PLAN AND PROVIDE THE TOTAL RUN LENGTH AND SLOPE
 OF THE DUCT. SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE WATER HEATERS, THE
 VENT DUCT AND TERMINATION CAP- SECS. 624.1, 503.2.3, &
 503.8 FBC FG. PLEASE SHOW THE TERMINATION CLEARANCE
 DISTANCES AS REQUIRED BY SEC. AND TABLE 503.8. SPECS
 FOR WATER HEATER AND CONCENTRIC VENT NOT PROVIDED.
  
  
 10) FAILED. FG0.1 & FG1.1: PROVIDE COMBUSTION AIR
 CALCULATIONS FOR THE PIZZA OVEN AND COOKING APPLIANCES
 AND INDICATE HOW THE AIR WILL BE PROVIDED- SEC. 304.1
 FBC FG. COMBUSTION AIR CALCULATIONS FOR THE PIZZA OVEN
 AND COOKING APPLIANCES NOT PROVIDED ON PLAN.
  
 11) FAILED. FG1.1: PROVIDE A CONDENSATE DISPOSAL PLAN
 FOR THE GAS-FIRED WATER HEATERS IN THE MEZZANINE- SECS.
 307.2, 307.4, & 307.5 FBC FG. SHOW THE TYPE AND SIZE OF
 CONDENSATE PIPING, PIPING RUN, REQUIRED PAN, PAN DRAIN
 LINE AND DISPOSAL LOCATION. PLEASE NOTE A NEUTRALIZING
 DEVICE WILL BE REQUIRED PER SEC. 803.1 FBC P. SPECS FOR
 THE WATER HEATER NOT PROVIDED TO VERIFY INTEGRAL
 NEUTRALIZING DEVICE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE