| 2022-03-15 13:20:18 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21121052 |
| | 3/15/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS RROM THE |
| | 1SRT REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. |
| | |
| | 2) FAILED. FG2.1 GAS RISER: B) SHOW THE TOTAL DEVELOPED |
| | LENGTH OF THE SYSTEM FROM THE METER TO THE MOST REMOTE |
| | APPLIANCE OUTLET- SEC. 402.4.1 FBC FG. NOT PROVIDED. |
| | |
| | 4) FAILED. FG1.1 & FG1.2: AN AUTOMATIC GAS SHUTOFF |
| | VALVE WITH MANUAL RESET IS REQUIRED TO BE CONNECTED TO |
| | THE HOOD FIRE SUPPRESSION SYSTEM PER SEC. 10.4.1 NFPA |
| | 96. THE VALVE DOES NOT APPEAR TO BE IN AN ACCESSIBLE |
| | LOCATION AS REQUIRED. PLEASE CORRECT THE PLAN AND |
| | PROVIDE THE VALVE SPECIFICATIONS. VALVE LOCATION NOT |
| | SHOWN ON RISER |
| | |
| | 6) FAILED. FG1.1: INDICATE THE TYPE OF CONCENTRIC DUCT |
| | ON THE PLAN AND PROVIDE THE TOTAL RUN LENGTH AND SLOPE |
| | OF THE DUCT. SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE WATER HEATERS, THE |
| | VENT DUCT AND TERMINATION CAP- SECS. 624.1, 503.2.3, & |
| | 503.8 FBC FG. PLEASE SHOW THE TERMINATION CLEARANCE |
| | DISTANCES AS REQUIRED BY SEC. AND TABLE 503.8. SPECS |
| | FOR WATER HEATER AND CONCENTRIC VENT NOT PROVIDED. |
| | |
| | |
| | 10) FAILED. FG0.1 & FG1.1: PROVIDE COMBUSTION AIR |
| | CALCULATIONS FOR THE PIZZA OVEN AND COOKING APPLIANCES |
| | AND INDICATE HOW THE AIR WILL BE PROVIDED- SEC. 304.1 |
| | FBC FG. COMBUSTION AIR CALCULATIONS FOR THE PIZZA OVEN |
| | AND COOKING APPLIANCES NOT PROVIDED ON PLAN. |
| | |
| | 11) FAILED. FG1.1: PROVIDE A CONDENSATE DISPOSAL PLAN |
| | FOR THE GAS-FIRED WATER HEATERS IN THE MEZZANINE- SECS. |
| | 307.2, 307.4, & 307.5 FBC FG. SHOW THE TYPE AND SIZE OF |
| | CONDENSATE PIPING, PIPING RUN, REQUIRED PAN, PAN DRAIN |
| | LINE AND DISPOSAL LOCATION. PLEASE NOTE A NEUTRALIZING |
| | DEVICE WILL BE REQUIRED PER SEC. 803.1 FBC P. SPECS FOR |
| | THE WATER HEATER NOT PROVIDED TO VERIFY INTEGRAL |
| | NEUTRALIZING DEVICE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |