2022-04-29 13:05:03ELECTRIC REVIEW FAILED
 1) RISER DIAGRAM DETAILS 3P-400-AMP FEEDING
 TRANSFORMER. PANEL SCEDULE DETAILS PANEL HC-1 FEEDING
 TRANSFORMER. PLEASE DETAIL CORRECT PANEL FEEDING
 TRANSFORMER. NEC 215.5
 2) PANEL SCHEDULE HC 1 DETAILS 125-AMP BREAKER FEEDING
 PANEL AC VIA TRANSFORMER. THIS TRANSFORMER FEEDS PANEL
 LC1. PLEASE CORRECT PANEL SCHEDULE AS APPROPRIATE. NEC
 215.5
 3) PRIMARY OVER CURRENT PROTECTION IS DETAILED AS
 125-AMP FOR 225 KVA TRANSFORMER APPEARS TO BE TOO
 SMALL. PLEASE CORRECT SIZE AS PER NEC 450.3(B)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  