| Plan Review Notes For Permit 21121052 |
| Permit Number |
21121052 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-04-29 13:05:03 | ELECTRIC REVIEW FAILED | | | 1) RISER DIAGRAM DETAILS 3P-400-AMP FEEDING | | | TRANSFORMER. PANEL SCEDULE DETAILS PANEL HC-1 FEEDING | | | TRANSFORMER. PLEASE DETAIL CORRECT PANEL FEEDING | | | TRANSFORMER. NEC 215.5 | | | 2) PANEL SCHEDULE HC 1 DETAILS 125-AMP BREAKER FEEDING | | | PANEL AC VIA TRANSFORMER. THIS TRANSFORMER FEEDS PANEL | | | LC1. PLEASE CORRECT PANEL SCHEDULE AS APPROPRIATE. NEC | | | 215.5 | | | 3) PRIMARY OVER CURRENT PROTECTION IS DETAILED AS | | | 125-AMP FOR 225 KVA TRANSFORMER APPEARS TO BE TOO | | | SMALL. PLEASE CORRECT SIZE AS PER NEC 450.3(B) | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|