| 2022-01-24 17:38:35 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21121052 |
| | 1/24/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A9.01 DETAILS 6 & 10: LABEL THE 3'4" |
| | MEASUREMENT FROM THE FINISHED FLOOR TO THE REFLECTIVE |
| | SURFACE OF THE MIRROR- SEC. 603.3 WPB. |
| | |
| | 2) A9.01 DETAILS 1, 3, 7, & 8: SHOW THE KNEE AND TOE |
| | CLEARANCE MEASUREMENTS FOR THE LAVATORIES IN THE |
| | DETAILS- SEC. 606.2 & FIGURES 306.2 & 306.3 FBC ACC. |
| | |
| | 3) P1.1: REMOVE THE BAR PLAN OVERLAY BLOCKING OUT THE |
| | UNDER-SLAB PIPING RUNS- SEC. 107.2.1 WPB. |
| | |
| | 4) P1.1, P1.2, & P4.1: THERE ARE NUMEROUS HANDSINKS AND |
| | FLOOR SINKS BELOW ICE MAKERS, BINS, GLASS WASHERS ETC. |
| | SHOWN DRAINING INTO THE GREASE WASTE LINE. REFER TO |
| | SEC. 1003.3.1 FBC P AND ROUT THE DRAINAGE FROM THOSE |
| | FIXTURES TO THE SANITARY SYSTEM- SEC. 1003.3.1 FBC P. |
| | THE LIST INCLUDES, BUT IS NOT LIMITED TO ITEMS 44, 45, |
| | 49, 66, 67, 68, 69, 103, 107, 108, 109, 134, & 135. |
| | PLEASE NOTE THAT ONLY FIXTURES DISCHARGING FATS, OILS, |
| | OR GREASE SHALL DRAIN INTO THE GREASE WASTE DISPOSAL |
| | SYSTEM. |
| | |
| | 5) ) P1.1, P1.2: SHOW THE GREASE WASTE LINE |
| | CONTINUATIONS TO THE GREASE INTERCEPTOR LOCATIONS AND |
| | INDICATE NEW OR EXISTING INTERCEPTORS- SECS. 107.2.1 |
| | WPB. REFER TO SECS. 1003.3- 1003.3.8 FBC P AND PROVIDE: |
| | A) GREASE WASTE CALCULATIONS. B) EQUIPMENT SCHEDULES |
| | INDICATING MAKES, MODELS AND CAPACITIES. C) GREASE |
| | WASTE PIPING LAYOUT SHOWING PIPING RUNS AND SIZES, |
| | LOCATIONS OF CLEANOUTS, VENTS, AND SAMPLING PORTS. |
| | PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR |
| | INSTALLATION OF THE GREASE INTERCEPTOR(S) AND THIS IS A |
| | PRELIMINARY REVIEW FOR COMPLIANCE. A COMPLETE SET OF |
| | PLANS, DETAILS, AND SPECIFICATIONS ARE REQUIRED FOR |
| | REVIEW UNDER THE SEPARATE PERMIT. |
| | |
| | 6) P1.1 & P1.3: PLACE TARGET NOTES AT THE GREASE WASTE |
| | PIPE CONTINUATIONS TO INDICATE WHERE THE PIPING IS |
| | RUNNING TO- SEC. 107.2.1 WPB. |
| | |
| | 7) P1.1 & P1.3: THE PLAN APPEARS TO SHOW THE FOLLOWING |
| | LIST OF FLOOR DRAINS AND FLOOR SINKS THAT ARE MISSING |
| | VENTS OR HAVE TRAPS THAT EXCEED THE MAXIMUM DISTANCE |
| | FROM TRAP TO VENT- SEE TABLE 909.1 & SEC. 915.1 FBC P- |
| | EFD-1 IN FEATURE BAR, FS-1 AT ITEM 103, EFD-1 IN PIZZA |
| | KITCHEN, FS-1 IN MAIN KITCHEN BY ITEM 92, EFD-1 IN MAIN |
| | KITCHEN, FS-1 BY ITEM 116. |
| | |
| | 8) P1.1 & P1.3: PROVIDE TRAP SEAL PROTECTION FOR THE |
| | EFD'S- SEC.1002.4.1 FBC P. PLEASE NOTE THAT |
| | BARRIER-TYPE SEAL PROTECTION DEVICES ARE NOT APPROVED |
| | BY THE WPB BUILDING DEPT. FOR USE IN COMMERCIAL |
| | KITCHENS. |
| | |
| | 9) P2.1, P2.2, P2.3: SHOW THE MAIN COLD WATER SUPPLY |
| | LINE INTO THE SPACE AND LOCATION SOF MAIN SHUTOFF VALVE |
| | AND WATER METER- SECS. 604.3 & 606.1 FBC P. |
| | |
| | 10) P2.1, P2.2, P2.3, & P4.2: SHOW THE WHA-A & WHA-B |
| | LOCATIONS- SEC. 604.9 FBC P. |
| | |
| | 11) P2.3: SHOW THE PIPE RISER CONTINUATIONS INTO THE |
| | MEZZANINE AND LOCATIONS OF SHUTOFF VALVES FOR DOWN |
| | FEEDING PIPES- SEC. 606.1 FBC P. |
| | |
| | 12) P4.2: PLEASE ADD THE FLOOR DRAINS, FLOOR SINKS, AND |
| | TROUGH DRAINS TO THE PLUMBING FIXTURE SCHEDULE- SECS. |
| | 412 & 413 FBC P. |
| | |
| | 13) P4.2: PROVIDE AN EQUIPMENT SCHEDULE FOR THE |
| | BACKFLOW PREVENTERS- SEC. 608.3 FBC P. |
| | |
| | 14) P4.3: THE WATER HEATER PIPING DIAGRAM DOES NOT SHOW |
| | THE HWR LINE CONNECTING TO THE COLD COLD WATER INLET |
| | PIPE OF THE WATER HEATER AND THE COLD WATER INLET PIPE |
| | OR THE HOT WATER RETURN CONNECTION OF THE THERMOSTATIC |
| | MIXING VALVE- SEC.607.2.2 WPB. |
| | |
| | 15) P2.2 & P4.3: SHOW THE WATER HEATER PAN DRAIN LINE |
| | RUNS AND DISCHARGE LOCATIONS- SEC. 504.7.2 FBC P. |
| | |
| | 16) P4.2: PROVIDE A SLAB REPAIR DETAIL- SEC. 107.2.1 |
| | WPB. |
| | |
| | 17) P4.3: REFER TO TABLE C403.2.10 FBC EC. AND PROVIDE |
| | HOT WATER PIPE INSULATION SPECIFICATIONS. |
| | |
| | 18) P4.2: DEFERRED SUBMITTALS- PROVIDE A LIST OF |
| | DEFERRED SUBMITTALS ON THE PLAN- SEC. 107.4.1 WPB. THE |
| | LIST SHALL INCLUDE ALL FIXTURES, DEVICES, APPLIANCES |
| | AND EQUIPMENT THAT DO NOT HAVE MAKES AND MODELS |
| | SPECIFIED ON THE PLANS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |