| 2022-01-18 15:14:19 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT- 21121052 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE ADD A NOTE TO THE MECHANICAL DRAWINGS STATING |
| | THAT THE KITCHEN HOODS WILL REQUIRE A SEPARATE PERMIT |
| | APPLICATION AND REVIEW AS THEY WILL NOT BE REVIEWED |
| | UNDER THIS PERMIT. |
| | |
| | 2) PLEASE ADDA NOTE TO THE MECHANICAL DRAWINGS STATING |
| | THAT THE REFRIGERATION EQUIPMENT WILL REQUIRE A |
| | SEPARATE PERMIT APPLICATION AND REVIEW AS THEY WILL NOT |
| | BE REVIEWED UNDER THIS PERMIT. |
| | |
| | 3) PLEASE SHOW THAT THE IN LINE GREASE DUCT EXHAUST |
| | FANS WILL MEET THE RATING REQUIREMENTS OF FBC M |
| | 506.5.1.2 |
| | |
| | 4) PLEASE SHOW HOW THE PENETRATIONS IN THE RATED |
| | SEPARATION WALLS WILL BE PROTECTED WHERE ALL DUCTS |
| | PENETRATE THE RATED WALLS. FBC M 607 |
| | |
| | 5) SHEET P4.1: I DO NOT SEE ANY PIZZA OVENS ON THE |
| | EQUIPMENT SCHEDULE. PLEASE EXPLAIN WHAT WILL BE USED. |
| | FBC 107.2.1 |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |