2022-01-25 09:08:421ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21121052
 1/25/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET FG0.1: THE GAS PIPE SIZING TABLE SHOWS AN
 INCORRECT TABLE FOR THE 2 PSI SYSTEM- SEE TABLE
 402.4(5) FBC FG. SEC. 402.3 FBC FG.
  
 2) FG2.1 GAS RISER:
 A) LABEL THE GAS APPLIANCES AND INDIVIDUAL BTUH LOADS
 AT EACH OUTLET- SEC. 402.4.1 FBC FG.
 B) SHOW THE TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM
 THE METER TO THE MOST REMOTE APPLIANCE OUTLET- SEC.
 402.4.1 FBC FG.
 C) SHOW THE BRANCH AND CUT PIPE LENGTH MEASUREMENTS-
 SEC. 402.4.2 FBC FG.
  
 3) FG0.1 DETAIL 1: SHOW PIPE UNIONS WITHIN 1 FT. OF
 EITHER SIDE OF THE REGULATOR- SEC. 410.2(7) FBC FG.
  
 4) FG1.1 & FG1.2: AN AUTOMATIC GAS SHUTOFF VALVE WITH
 MANUAL RESET IS REQUIRED TO BE CONNECTED TO THE HOOD
 FIRE SUPPRESSION SYSTEM PER SEC. 10.4.1 NFPA 96. THE
 VALVE DOES NOT APPEAR TO BE IN AN ACCESSIBLE LOCATION
 AS REQUIRED. PLEASE CORRECT THE PLAN AND PROVIDE THE
 VALVE SPECIFICATIONS.
  
 5) FG1.1: THE PLAN APPEARS TO SHOW THE TANKLESS WATER
 HEATER VENT PENETRATING THE EXIT STAIRWAY WHICH IS
 PROHIBITED IN ACCORDANCE WITH SEC. 1023.5 FBC B. PLEASE
 RELOCATE THE VENT.
  
 6) FG1.1: INDICATE THE TYPE OF CONCENTRIC DUCT ON THE
 PLAN AND PROVIDE THE TOTAL RUN LENGTH AND SLOPE OF THE
 DUCT. SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE WATER HEATERS, THE
 VENT DUCT AND TERMINATION CAP- SECS. 624.1, 503.2.3, &
 503.8 FBC FG. PLEASE SHOW THE TERMINATION CLEARANCE
 DISTANCES AS REQUIRED BY SEC. AND TABLE 503.8.
  
 7) FG1.1: PROVIDE AN EQUIPMENT TAG FOR THE GAS-FIRE
 APPLIANCE DOWNSTREAM OF THE PIZZA OVEN- ITEM 24- SEC.
 107.2.1 WPB.
  
 8) FG2.1 GAS RISER: LABEL THE GAS APPLIANCES AND
 INDIVIDUAL BTUH LOADS AT EACH OUTLET- SEC. 402.4.1 FBC
 FG.
  
 9) FG0.1 & FG1.1: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE GAS-FIRED PIZZA OVEN AND COOKING APPLIANCES -
 SEC. 623.1 FBC FG.
  
 10) FG0.1 & FG1.1: PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE PIZZA OVEN COOKING APPLIANCES AND INDICATE HOW
 THE AIR WILL BE PROVIDED- SEC. 304.1 FBC FG.
  
 11) FG1.1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE
 GAS-FIRED WATER HEATERS IN THE MEZZANINE- SECS. 307.2,
 307.4, & 307.5 FBC FG. SHOW THE TYPE AND SIZE OF
 CONDENSATE PIPING, PIPING RUN, REQUIRED PAN, PAN DRAIN
 LINE AND DISPOSAL LOCATION. PLEASE NOTE A NEUTRALIZING
 DEVICE WILL BE REQUIRED PER SEC. 803.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  