| 2022-01-25 09:08:42 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21121052 |
| | 1/25/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET FG0.1: THE GAS PIPE SIZING TABLE SHOWS AN |
| | INCORRECT TABLE FOR THE 2 PSI SYSTEM- SEE TABLE |
| | 402.4(5) FBC FG. SEC. 402.3 FBC FG. |
| | |
| | 2) FG2.1 GAS RISER: |
| | A) LABEL THE GAS APPLIANCES AND INDIVIDUAL BTUH LOADS |
| | AT EACH OUTLET- SEC. 402.4.1 FBC FG. |
| | B) SHOW THE TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM |
| | THE METER TO THE MOST REMOTE APPLIANCE OUTLET- SEC. |
| | 402.4.1 FBC FG. |
| | C) SHOW THE BRANCH AND CUT PIPE LENGTH MEASUREMENTS- |
| | SEC. 402.4.2 FBC FG. |
| | |
| | 3) FG0.1 DETAIL 1: SHOW PIPE UNIONS WITHIN 1 FT. OF |
| | EITHER SIDE OF THE REGULATOR- SEC. 410.2(7) FBC FG. |
| | |
| | 4) FG1.1 & FG1.2: AN AUTOMATIC GAS SHUTOFF VALVE WITH |
| | MANUAL RESET IS REQUIRED TO BE CONNECTED TO THE HOOD |
| | FIRE SUPPRESSION SYSTEM PER SEC. 10.4.1 NFPA 96. THE |
| | VALVE DOES NOT APPEAR TO BE IN AN ACCESSIBLE LOCATION |
| | AS REQUIRED. PLEASE CORRECT THE PLAN AND PROVIDE THE |
| | VALVE SPECIFICATIONS. |
| | |
| | 5) FG1.1: THE PLAN APPEARS TO SHOW THE TANKLESS WATER |
| | HEATER VENT PENETRATING THE EXIT STAIRWAY WHICH IS |
| | PROHIBITED IN ACCORDANCE WITH SEC. 1023.5 FBC B. PLEASE |
| | RELOCATE THE VENT. |
| | |
| | 6) FG1.1: INDICATE THE TYPE OF CONCENTRIC DUCT ON THE |
| | PLAN AND PROVIDE THE TOTAL RUN LENGTH AND SLOPE OF THE |
| | DUCT. SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE WATER HEATERS, THE |
| | VENT DUCT AND TERMINATION CAP- SECS. 624.1, 503.2.3, & |
| | 503.8 FBC FG. PLEASE SHOW THE TERMINATION CLEARANCE |
| | DISTANCES AS REQUIRED BY SEC. AND TABLE 503.8. |
| | |
| | 7) FG1.1: PROVIDE AN EQUIPMENT TAG FOR THE GAS-FIRE |
| | APPLIANCE DOWNSTREAM OF THE PIZZA OVEN- ITEM 24- SEC. |
| | 107.2.1 WPB. |
| | |
| | 8) FG2.1 GAS RISER: LABEL THE GAS APPLIANCES AND |
| | INDIVIDUAL BTUH LOADS AT EACH OUTLET- SEC. 402.4.1 FBC |
| | FG. |
| | |
| | 9) FG0.1 & FG1.1: SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR THE GAS-FIRED PIZZA OVEN AND COOKING APPLIANCES - |
| | SEC. 623.1 FBC FG. |
| | |
| | 10) FG0.1 & FG1.1: PROVIDE COMBUSTION AIR CALCULATIONS |
| | FOR THE PIZZA OVEN COOKING APPLIANCES AND INDICATE HOW |
| | THE AIR WILL BE PROVIDED- SEC. 304.1 FBC FG. |
| | |
| | 11) FG1.1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE |
| | GAS-FIRED WATER HEATERS IN THE MEZZANINE- SECS. 307.2, |
| | 307.4, & 307.5 FBC FG. SHOW THE TYPE AND SIZE OF |
| | CONDENSATE PIPING, PIPING RUN, REQUIRED PAN, PAN DRAIN |
| | LINE AND DISPOSAL LOCATION. PLEASE NOTE A NEUTRALIZING |
| | DEVICE WILL BE REQUIRED PER SEC. 803.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |