| Plan Review Notes For Permit 21121052 |
| Permit Number |
21121052 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-12-29 12:52:50 | FIRE PROVISO NOTES: | | | 1.ALL FIRE ALARM SYSTEM WORK SHALL BE DONE BY A | | | CERTIFIED FIRE ALARM CONTRACTOR AND COMPLY WITH NFPA | | | 72. A SEPARATE SHOP DRAWING IS REQUIRED TO BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION | | | BUREAU PRIOR TO ANY WORK ON THE SYSTEM. | | | 2.THE LIFE SAFETY SYSTEMS, FIRE SPRINKLER AND/OR FIRE | | | ALARM, SHALL REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION | | | PERIOD. | | | 3.ENSURE THAT EMERGENCY AND EXIT LIGHTING IS SUPPLIED | | | FOR ALL EXITS AND EXIT PATHS. THIS INCLUDES WALK IN | | | UNITS. A COMBINATION EXIT/EMERGENCY UNIT IS ACCEPTABLE. | | | |
|