Plan Review Notes
Plan Review Notes For Permit 21121052
Permit Number 21121052
Review Stop B
Sequence Number 1
Notes
Date Text
2022-02-09 12:54:06RESTAURANT BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) RAMP HAND RAIL EXTENSION SHOULD NOT TURN AROUND THE
 CORNER AS SHOWN ON DRAWING A1.1.1 FBC A 505.10.1 TOP
 AND BOTTOM EXTENSION AT RAMPS.
 RAMP HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE
 LANDING FOR 12 INCHES (305 MM) MINIMUM BEYOND THE TOP
 AND BOTTOM OF RAMP RUNS. EXTENSIONS SHALL RETURN TO A
 WALL, GUARD, OR THE LANDING SURFACE, OR SHALL BE
 CONTINUOUS TO THE HANDRAIL OF AN ADJACENT RAMP RUN.
  
 2) PLEASE SHOW THE REQUIRED HANDRAILS AT ALL OF THE
 RAMPS FBC 405.8
  
 3) PLEASE SHOW THE DOOR MANEUVERING CLEARANCE ON THE
 INTERIOR SIDE OF RESTROOM (DOOR 113) (18" BESIDE THE
 LATCH SIDE) FBC 404.2.4
  
 4) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR
 DIMENSIONS FROM THE FINISHED FLOOR TO THE BOTTOM OF THE
 "REFLECTIVE SURFACE" FBC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 5) PLEASE SHOW THE HOURLY FIRE RATING FOR THE DOORS
 LOCATED IN THE FIRE PARTITIONS FBC 716
  
 6) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD
 FBC WPB 107.3.4
  
  