| Plan Review Notes For Permit 21121037 |
| Permit Number |
21121037 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-07 07:48:08 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT-21121037 | | | 1/7/22 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | BACKFLOW PREVENTER INDICATING THE MAKE, MODEL, AND SIZE | | | OF THE DEVICE. THE DOCUMENTATION SHALL INDICATE THE | | | DEVICE IS LEAD FREE AND IS ON THE APPROVED DEVICE LIST | | | PUBLISHED BY THE UNIVERSITY OF SOUTHERN CALIFORNIA | | | (USC). PLEASE CONTACT DEPARTMENT OF PUBLIC UTILITY | | | FIELD CUSTOMER SERVICE AT 561-822-2240 FOR DOCUMENTED | | | CONFIRMATION THAT THE PROPOSED BACKFLOW PREVENTION | | | DEVICE COMPLIES WITH CITY REQUIREMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|