2022-01-12 08:13:4701/05/22 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS A RECORD OF AN LP
 TANK BEING INSTALLED. WILL THIS TANKLESS BE INCLUDED IN
 THE LP SERVICE. IF YOU WOULD, PLEASE PROVIDE A GAS
 RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS.
  
 2. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP
 CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 4. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1, AND THE PLUMBING PERMIT WILL BE
 CHANGED TO A GAS.
  
 5. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD OF THE EXISTING SYSTEM. REFER TO THE 2020 FBC
 RES. SEC. G2413.
  
 6. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR
 NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. WOULD YOU PLEASE SUBMIT THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD USED IN THE DESIGN OF THIS SYSTEM PER
 2020 FBC RES. SEC. G2413.3.
  
 8. THIS TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN,
 AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER THE
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. G2421.1.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1.
  
 10. PLEASE LABEL AND SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC FG SEC
 410.2. OR 2020 FBC RES. SEC G2421.2.
  
 11. PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2020 FBC RES. SEC. G2420.5.
  
 12. A SUB ELECTRICAL PERMIT IS REQUIRED FOR IGNITION
 SOURCE PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 13. GAS UNITS REQUIRE CONDENSATE, AND THEY NEED TO BE
 1' AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC R318.5.
  
 14. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 15. WOULD YOU PLEASE SHOW AND LABEL THE DRIP LEG PER
 THE 2020 FBC RES. SEC. G2419.2.
  
 16. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720