| Date |
Text |
| 2022-06-15 11:32:22 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 21120968 |
| | 6/15/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P-4: PROVIDE TDH CALCULATIONS AND THE POOL |
| | PUMP CURVE ON THE PLAN SHEET- SECS. 4.4.9, 4.4.9.1 |
| | ANSI/APSP/ICC-7 & R4501.7.2 & R4501.7.3 FBC RES. |
| | |
| | 2) P-3 & P-4: IF AN AUTOFILL IS TO BE INSTALLED, PLEASE |
| | SHOW THE LOCATIONS OF THE DEVICE AND THE REQUIRED |
| | BACKFLOW PREVENTER TO PROTECT THE POTABLE WATER SYSTEM- |
| | SEC. R4501.9 & P2902.3 FBC RES. PLEASE INDICATE THE |
| | TYPE OF BACKFLOW PREVENTER TO BE INSTALLED- TABLE |
| | P2902.3 FBC RES. |
| | |
| | 3) PLEASE NOTE A RPZ BACKFLOW PREVENTER IS REQUIRED AT |
| | THE WATER METER TO PROTECT THE POTABLE WATER SERVICE- |
| | SEC. C & D WPB UTILITIES CROSS-CONNECTION MANUAL. THE |
| | DEVICE SHALL BE INSTALLED UNDER A SEPARATE PERMIT- SEC. |
| | 105.1 WPB. |
| | |
| | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | AQUASTAR ANTI-ENTRAPMENT CHANNEL DRAIN ASSEMBLY |
| | INCLUDING SUCTION OUTLET COVER AND FRAME- SEC. |
| | R4501.6.2 & R4501.6.6 FBC RES. |
| | |
| | 5) THE $20,000 VALUE ON THE APPLICATION APPEARS LOW FOR |
| | THE NEW POOL INSTALLATION. PLEASE PROVIDE AN ITEMIZED |
| | COST BREAKDOWN FOR THE PROJECT THAT INCLUDES, LABOR, |
| | MATERIALS, POOL EQUIPMENT, SITE WORK AND DESIGN FEES- |
| | SEC. 109.3 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |