2022-02-18 10:55:57PLAN DENIED
 1) PROVIDE CHANGE OUT FORM AND AHRI SHEET FOR MAIN
 HOUSE.
 EQUIPMENT SCHEDULE SAYS EXISTING PLAN SAYS NEW A/C.
 SECTION 107.2.1 FBC
 2) PROVIDE MECHANICAL EQUIPMENT SIZING CALCULATION
 FOR NEW ADDITION. R403.7.1 2020 FLORIDA ENERGY CODE
 3) REFER TO SECTION M1502.3.1 CLOTHES DRYER EXHAUST
 TERMINATION OUTLET AND PASSAGEWAY 2020 FBC (R)
 4) 12 X 8 TRANSFER GRILL IS NOT REQUIRED IN BATHROOMS
 SECTION M1602.3 BALANCED RETURN # 3 2020 FBC (R)
 5) PLEASE PROVIDE THE CALCULATION ON HOW HIGH THE
 UNDERCUT OF THE DOOR WOULD HAVE TO BE FOR A RETURN AIR
 OF THE ONE TON SYSTEM. SECTION 107 FBC.
 6) EQUIPMENT SCHEDULE AND ENERGY CALCULATION SHOW
 17 SEER NOTE AT CONDENSER SAY 15 SEER PLEASE FIX.
 7)) PROVIDE CFM ON BATHROOM EXHAUST
 SECTION 1507.4 FBC (R) 2020
 8) PROVIDE MANUFACTURE SPECIFICATION ON KITCHEN
 EXHAUST HOOD. SECTION M1503.4 MAKEUP AIR REQUIRED
 2020 FBC (R)