| 2022-02-18 10:55:57 | PLAN DENIED | | | 1) PROVIDE CHANGE OUT FORM AND AHRI SHEET FOR MAIN | | | HOUSE. | | | EQUIPMENT SCHEDULE SAYS EXISTING PLAN SAYS NEW A/C. | | | SECTION 107.2.1 FBC | | | 2) PROVIDE MECHANICAL EQUIPMENT SIZING CALCULATION | | | FOR NEW ADDITION. R403.7.1 2020 FLORIDA ENERGY CODE | | | 3) REFER TO SECTION M1502.3.1 CLOTHES DRYER EXHAUST | | | TERMINATION OUTLET AND PASSAGEWAY 2020 FBC (R) | | | 4) 12 X 8 TRANSFER GRILL IS NOT REQUIRED IN BATHROOMS | | | SECTION M1602.3 BALANCED RETURN # 3 2020 FBC (R) | | | 5) PLEASE PROVIDE THE CALCULATION ON HOW HIGH THE | | | UNDERCUT OF THE DOOR WOULD HAVE TO BE FOR A RETURN AIR | | | OF THE ONE TON SYSTEM. SECTION 107 FBC. | | | 6) EQUIPMENT SCHEDULE AND ENERGY CALCULATION SHOW | | | 17 SEER NOTE AT CONDENSER SAY 15 SEER PLEASE FIX. | | | 7)) PROVIDE CFM ON BATHROOM EXHAUST | | | SECTION 1507.4 FBC (R) 2020 | | | 8) PROVIDE MANUFACTURE SPECIFICATION ON KITCHEN | | | EXHAUST HOOD. SECTION M1503.4 MAKEUP AIR REQUIRED | | | 2020 FBC (R) | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|