| Date |
Text |
| 2021-12-30 06:57:13 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21120958 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE NEW |
| | ADDITION. FBC EC 101.5.1.1.2 |
| | |
| | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS FOR THE NEW ADDITION. FBC EC R403.7.1 |
| | |
| | 3) PLEASE PROVIDE THE LIKE FOR LIKE CHANGE OUT FORM FOR |
| | THE MAIN HOUSE AHU AND CONDENSING UNIT CHANGE OUT. FBC |
| | 107.2.1 |
| | |
| | 4) PLEASE SHOW THE RETURN AIR PATH FROM EACH HABITUAL |
| | ROOM WITH A DOOR BETWEEN THE ROOMS AND THE AHU WITH |
| | BOTH AHU?S. FBC RES M1602.3 |
| | |
| | 5) PLEASE SHOW THE CONDENSATE PIPING MATERIAL, SIZE AND |
| | TERMINATION LOCATION FOR BOTH AHU?S. FBC RES M1411.3 |
| | |
| | 6) PLEASE SHOW THE EXHAUST FOR THE BATHROOMS AND THE |
| | EXHAUST TERMINATION LOCATIONS. FBC RES M1507.4 |
| | |
| | 7) IS THERE GOING TO BE A DUCTED KITCHEN HOOD? IF SO |
| | PLEASE PROVIDE THE CFM?S OF THE HOOD EXHAUST MOTOR. FBC |
| | RES M1503.4 |
| | |
| | 8) PLEASE SHOW THE DRYER EXHAUST DUCT AND TERMINATION |
| | LOCATION. FBC RES M1502.3 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |