| 2022-01-24 20:57:12 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. EQUIPMENT GROUNDING CONDUCTOR SHOWN FROM METER CAN |
| | TO SERVICE DISCONNECTING MEANS. THIS IS NOT PERMITTED. |
| | EQUIPMENT GROUNDING CONDUCTOR ORIGINATES ON LOAD SIDE |
| | OF 1ST DISCONNECTING MEANS. PLEASE REMOVE. NEC 250.24 |
| | |
| | 2. INCORRECT SIZE GEC SHOWN FOR COPPER WATER PIPE. |
| | MINIMUM #4 CU PLEASE PROVIDE CORRECTION. NEC 250.66 |
| | |
| | 3. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP |
| | CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. |
| | PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE |
| | E3703.4, E3901.6 |
| | |
| | 4. SHOW SMOKE/CO ALARMS OR ADD NOTE THAT SMOKE/CO |
| | ALARMS MUST BE UP TO CURRENT CODE PER FBC-R 314 AND 315 |
| | |
| | 5. PROVIDE NOTE ON PLAN THAT ARC-FAULT PROTECTION WILL |
| | BE INSTALLED PER NEC 210.12A AND 210.12B |
| | |
| | 6. PROVIDE NOTE ON PLAN THAT TAMPERPROOF RECEPTACLES |
| | WILL BE INSTALLED PER NEC 406.12 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |