2022-04-06 14:23:192ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21120951
 4/6/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENT #2 FROM THE
 1ST REVIEW PRINTED BELOW WITH ADDITIONAL NOTES.
  
 2) FAILED. LSP: PLEASE CORRECT THE PLUMBING FIXTURE
 CALCULATION TABLE TO REFLECT THE MIXED OCCUPANCIES OF
 A2, F2, M, S. REFER TO SEC. 403.1.1 FBC P- FOR
 CALCULATIONS INVOLVING MULTIPLE OCCUPANCIES, FRACTIONAL
 NUMBERS FOR EACH OCCUPANCY SHALL FIRST BE SUMMED AND
 THEN ROUNDED UP TO THE NEXT WHOLE NUMBER. THE BUILDING
 PLAN REVIEWER IS DISPUTING THE OCCUPANCY
 CLASSIFICATIONS AND OCCUPANT LOAD CALCULATIONS. A
 COMPLETE REVIEW OF THE PLUMBING FIXTURE CALCULATIONS
 CANNOT BE ACCOMPLISHED AT THIS TIME. AS STATED IN THE
 1ST REVIEW COMMENT, FIXTURE COUNTS FOR MIXED
 OCCUPANCIES SHALL BE CALCULATED USING FRACTIONAL
 NUMBERS FOR EACH OCCUPANCY CLASSIFICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  