| 2022-04-13 08:06:54 | 2ND REVIEW FMC |
| | PERMIT: 21120951 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS S-1, E-3.0, F2.0 CLEARLY SHOWS THAT AREAS OF |
| | THE USE OF THE SPACE THAT IS CALLED BUSINESS IS |
| | ASSEMBLY. FMC 403.3.1.1 TELLS US WE MUST CALCULATE |
| | VENTILATION RATES FOR EACH SPACE ACCORDING TO ITS USE. |
| | PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THE |
| | BUSINESS AREA OF THIS SPACE BASED UPON IT?S USE. SINCE |
| | THERE IS A COFFEE BAR WE MUST USE THE OCCUPANCY |
| | CLASSIFICATION OF BARS, COCKTAIL LOUNGES AND WITH NO |
| | KITCHEN OR COOKING WE CANNOT USE DINING ROOMS FOR THE |
| | USE OF SPACE WHERE THE SEATING IS LOCATED FOR THE |
| | PUBLIC TO WATCH THE ROASTING PROCESS AND THE LAB AREA. |
| | |
| | 2) THE BUILDING CODE WILL REQUIRE A 1-HOUR SEPARATION |
| | BETWEEN THE BUSINESS AND F-2 OCCUPANCIES. PLEASE SHOW |
| | HOW THIS WILL AFFECT THE EXHAUST DESIGN FOR THE |
| | ROASTERS AND THE MECHANICAL SYSTEMS. FMC 607 |
| | |
| | 3) THE NEW LOUVER AND DUCTWORK DESIGN PROVIDED FOR THE |
| | VELOCITY TO MOVE THE ROASTER EXHAUST THROUGH THE |
| | DUCTWORK AND OUT THE TERMINATION LOCATION DID NOT SHOW |
| | THE FAN REQUIRED FOR THIS DESIGN. PLEASE PROVIDE THE |
| | SPECS FOR THE FAN AND SHOW THE LOCATION OF THE FAN IN |
| | THIS SYSTEM. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |