| 2022-01-14 06:03:56 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21120951 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET E2.0 INDICATES 3 WALK IN REFRIGERATORS. THESE, |
| | LIKE THE WALK IN COOLER, WILL NEED A SEPARATE PERMIT |
| | AND REVIEW AS THEY WILL NOT BE REVIEWED UNDER THIS |
| | PERMIT. |
| | |
| | 2) SHEET E2.0 INDICATES KITCHEN EQUIPMENT. PLEASE SHOW |
| | HOW THIS EQUIPMENT WILL MEET FBC M 507 |
| | |
| | 3) PLEASE PROVIDE THE SPECS FOR THE BATH EXHAUST FANS. |
| | PLEASE SHOW THE BATH EXHAUST FANS MEET THE MINIMUM |
| | CFM?S REQUIRED FOR EACH WATER CLOSET AND URINAL. FBC M |
| | TABLE 403.3.1.1 FOOTNOTE F |
| | |
| | 4) SHEET M3.1: PLEASE SHOW THE KITCHEN IN THE OUTDOOR |
| | AIR CALCULATIONS. PLEASE SHOW THE REQUIRED OUTDOOR AIR |
| | FOR THIS AREA AND THE EXHAUST REQUIRED FOR THIS |
| | KITCHEN. FBC M 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | 5) SHEET M3.1: PLEASE CORRECT THE OUTDOOR AIR |
| | CALCULATION FOR THE BAR/SALES AREA. THIS AREA BEING |
| | OPEN WOULD NEED TO BE CALCULATED AT THE MOST |
| | RESTRICTIVE WHICH WOULD BE THE OCCUPANCY CLASSIFICATION |
| | OF BAR, COCKTAIL LOUNGES FROM FBC M TABLE 403.3.1.1 |
| | |
| | 6) ONCE THE CORRECTIONS ARE MADE PLEASE PROVIDE AN AIR |
| | BALANCE REPORT THAT INCLUDES ALL EXHAUST, MAKEUP AIR, |
| | COMBUSTION AIR AND OUTDOOR AIR REQUIRED FOR THIS TENANT |
| | SPACE. FBC 107.2.1 |
| | |
| | 7) THERE IS A LETTER IN THE SUPPORTING DOCS FROM BMC |
| | CONSULTING DATED NOV. 4, 2021. I AM JUST SEEING THIS |
| | LETTER TODAY AS I WAS NOT NOTIFIED THAT THIS LETTER HAD |
| | BEEN SUBMITTED. IS THIS THE RATIONAL ANALYSIS REQUESTED |
| | BY ROBERT BROWN FOR THE INSTALLATION OF THE ROASTERS |
| | AND THE EXHAUST DUCTING FOR THIS PERMIT? IF IT IS THEN |
| | PLEASE SUBMIT INFORMATION TO BACK UP THESE COMMENTS. |
| | |
| | 8) AS A REMINDER, A MECHANICAL PERMIT WILL STILL BE |
| | REQUIRED FOR THE INSTALLATION OF THE ROASTER'S EXHAUST |
| | DUCT. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |