| 2022-01-18 14:12:08 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 21120951 |
| | W. P. B. PERMIT:21020294 |
| | ADD: 1016 CLARE UNIT: 4 BUILT IN 1946 |
| | CONT: PERK CONSTRUCTION INC. / U-21885 |
| | TEL: 561-401-5984 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JAN. 18TH/ 2022 |
| | ACTION: DENIED |
| | |
| | 1) THE STATED VALUE OF THE REVISION IS $12,000 DOLLARS, |
| | EXTREMELY LOW. THE SHOWN WORK IN THE REVISION SHOWS NEW |
| | GLAZED WALL BETWEEN THE LAB AND NEW ASSEMBLY AREA, NEW |
| | BAR SETTING, EQUIPMENT AND SEATING, 2 NEW COUNTERS AND |
| | SEATING, NEW TABLES AND CHAIRS QUANTITY UNKNOWN NOT |
| | SHOWN ON THE LIFE SAFETY PLAN, AND MERCANTILE AREA NO |
| | KIOSK OR SALES COUNTERS SHOWN AND NEW WHAT APPEARS TO |
| | BE COUNTER, PLUMBING, ELECTRICAL, AND MECHANICAL ALL OF |
| | THESE ITEMS ARE TO BE PART OF THE REVISION AND UPDATED |
| | VALUE OF THE REVISION. |
| | |
| | 109.3 BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) THE LIFE SAFETY SHEET: |
| | 2A)(1) HEADING 1003.5.1 ELEVATION CHANGE A SINGLE STEP |
| | WITH A MAXIMUM RISER OF 7 INCHES IS PERMITTED FOR |
| | BUILDINGS WITH OCCUPANCIES IN GROUP F AND S OCCUPANCIES |
| | AT EXTERIOR DOORS NOT REQUIRED TO BE ACCESSIBLE BY |
| | CHAPTER 11. |
| | PLEASE NOTE THERE IS A PARTIAL OCCUPANCY CHANGE TO AN |
| | A2 OCCUPANCY WITH AN INCREASED OCCUPANT LOAD OF OVER 50 |
| | OCCUPANTS REQUIRING 2 ACCESSIBLE EXITS. |
| | |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| | EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | |
| | 2A)(2) THE LIFE SAFETY SHEET INCLUDES THE BACK EXIT |
| | STAIRS IN REVISION 3. SHEET A1.0 BACK EXTERIOR STAIRS |
| | STATES SEE DETAIL 7/A1.1 AND S1.0. THIS REVIEW THERE |
| | WAS NO SHEET S1.0. SHEET A1.1 REVISION # 2 STATED THAT |
| | THE BACK EXTERIOR STAIRS WAS TO BE PREMANUFACTURED |
| | METAL STAIR AND GUARDRAIL. PLEASE PROVIDE DETAILS FOR |
| | THE FOUNDATION OF STAIRWAY VERTICAL STEEL, RISE AND RUN |
| | OF STAIRS AND VERTICAL DISTANCE FROM THE INTERIOR |
| | FINISH FLOOR TO THE EXTERIOR TOP LANDING. 107.2.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2B) WITH THE NEW A2 OCCUPANCY PLEASE SHOW HOW THE BACK |
| | EXIT IS TO COMPLY WITH ACCESS TO THE PUBLIC WAY (2017 |
| | FBC-BUILDING 1028.5 AND VERTICAL ACCESSIBILITY 2017 |
| | FBC-ACCESSIBILITY SECTION 201.1.1. |
| | |
| | 2C) OCCUPANT LOAD TABLE SHOWS 2 OCCUPANT LOAD FACTORS |
| | ONE AT 60 THE OTHER AT 80. PLEASE SEE TABLE 1004.1.2 |
| | MERCANTILE IS TO BE 60 GROSS. |
| | |
| | 2D) PLUMBING FIXTURE COUNT IS FOR F2 ONLY, NEEDS TO |
| | UPDATE FOR THE A2 OCCUPANCY AND MERCANTILE OCCUPANCY . |
| | 2017 FBC-BUILDING TABLE 2902.1. |
| | |
| | 2E)(1) THE EXIT PASSAGEWAY SHOWING THE ONE HOUR FIRE |
| | RATING AND WINDOWS PLEASE NOTE THE WINDOWS ARE PART OF |
| | REVISION # 2 SHOULD SHOW AS A REVISION. 107.2.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2E(2) THE 1 HOUR EXIT PASSAGEWAY WINDOWS THAT ARE SHOWN |
| | ON SHEET A1.1 DETAIL 6 REV. # 2 STATES NFPA 80 |
| | COMPLIANCE STYLE CASEMENT WINDOWS. PLEASE NOTE CASEMENT |
| | STYLE WINDOWS ARE HINGES ON EITHER THE LEFT AND RIGHT |
| | AND OPEN OUT, PLEASE PROVIDE PRODUCT TESTING REPORT FOR |
| | 1 HOUR CASEMENT WINDOWS COMPLYING WITH 2017 |
| | FBC-BUILDING TABLE 716.6. |
| | |
| | 2F) PLEASE NOTE THE 2 NEW COMPRESSORS CU-3 AND CU-5 |
| | BOTH ARE LOCATED IN A FLOOD ZONE PLEASE PROVIDE THE TOP |
| | OF THE FINISH SLAB AND OR IF TO BE INSTALLED ON A STAND |
| | PROVIDE THE PRODUCT APPROVAL FOR THE A/C STAND AND THE |
| | TOP HEIGHT OF THE STAND AND ELEVATION IN NAV88. |
| | |
| | 3) SHEET A1.3 DETAILS 1, 2 & 5 SHOW A GLAZES WALL |
| | SYSTEM SITTING ON A KNEE WALL WITH CANTILEVERED COUNTER |
| | THE PLANS ARE SILENT AS TO HOW THE WALL WILL GAIN |
| | LATERAL SUPPORT SINCE THERE ARE NO STUDS NOR MULLIONS |
| | GOING FROM FLOOR TO THE EXISTING BEAM ABOVE. HOW WILL |
| | COMPLIANCE WITH 2017 FBC-BUILDING CODE SECTION 1604.3 |
| | AND TABLE 1604.3. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |