Plan Review Notes
Plan Review Notes For Permit 21120946
Permit Number 21120946
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-11-29 13:28:591. PLEASE CLARIFY THE FINAL HEIGHT OF THE PROPOSED
 WIRELESS FACILITIES POLE AND IDENTIFY THE REFERENCED
 POLE FOR COMPATIBLE HEIGHT WITHIN THE SAME ROW.
  
 SPECIFIC PURPOSE SURVEY SIGNED BY THOMAS CLANCY ON
 11/10/19 STATES A NEW STANDALONE 30??? HEIGHT POLE,
 WITH TOP ELEVATION AT 33???. THE REFERENCED POLE FOR
 COMPATIBLE HEIGHT IS 26???. THE PROPOSED WIRELESS
 FACILITIES POLE MUST BE LESS THAN OR EQUAL TO THE
 HEIGHT OF THE REFERENCED POLE ALONG THE SAME PORTION OF
 ROW. PLEASE ADJUST TOTAL WCF POLE HEIGHT TO BE AT OR
 LESS THAN 26???.
  
  
 SPECIFIC PURPOSE SURVEY SIGNED BY THOMAS CLANCY ON
 1/28/22 STATES THE NEW STANDALONE POLE IS AT 25??? IN
 HEIGHT, WITH A TOP ELEVATION AT 28???. THE REFERENCED
 POLE FOR COMPATIBLE HEIGHT IS 26???. THE PROPOSED
 WIRELESS FACILITIES POLE MUST BE LESS THAN OR EQUAL TO
 THE HEIGHT OF THE REFERENCED POLE ALONG THE SAME
 PORTION OF ROW. PLEASE ADJUST TOTAL WCF POLE HEIGHT TO
 BE AT OR LESS THAN 26???.
  
 THE PLAN VIEW SHEET FROM DRAFTPROS SUGGESTS 30???
 HEIGHT POLES WITHIN THE ROW AS REFERENCE, AND A 30???
 PROPOSED WCF POLE.
  
 NEW POLE ELEVATIONS AND PHOTO SIM SHEETS ALSO SUGGEST A
 30??? PROPOSED POLE.
  
  
 2. PLEASE PROVIDE PROPOSED UNDERGROUND POWER ROUTE FOR
 THE ELECTRICAL CONNECTION, WHERE IS POWER BEING DRAWN
 TO AND FROM?
  
 STAFF MUST CONFIRM THAT THE POWER SOURCE IS LOCATED
 WITHIN THE ROW OR WITHIN A GENERAL UTILITIES EASEMENT.
  
 PLEASE INCLUDE BORING/HANDHOLE LOCATIONS, UNDERGROUND
 BORING PROFILE, DEPTH OF LINES AND DIMENSIONAL RELATION
 TO ANY UNDERGROUND UTILITIES OR STREET TREES. ANY
 EXCAVATION WORK MUST MAINTAIN A MINIMUM OF 8???
 CLEARANCE FROM STREET TREES.
  
  
 3. PROPOSED POLE DESIGN SHALL MEET CITY STANDARDS FOR
 STEALTH DESIGN AND COLOR. RAYCAP INTEGRATED POLE - RAL
 7044 (SILK GREY) OR EQUIVALENT.
  
 PHOTO SIM SHEETS REFERENCE LIGHT GREY, PLEASE MATCH RAL
 7044 (SILK GREY).
  
 4. OVERALL SITE PLAN AND SURVEY SHOULD PROVIDE FULL
 SCOPE OF PROJECT/WORK AREA. INCLUDING THE POWER RUN AND
 CONNECTIONS TO/FROM WCF POLE.
  
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 822-1426 [email protected]