| Plan Review Notes For Permit 21120944 |
| Permit Number |
21120944 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-04-06 11:12:17 | GARAGE BEAM STRENGTHENING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING S-1.10 SHOWS METAL BRACKETS - PLEASE SHOW | | | THE LENGTH OF THE BRACKET ALONG THE BOTTOM OF THE BEAM | | | - OR A BRACKET DIMENSION DIAGRAM. | | | | | | 2) PLEASE STATE THE MANUFACTURE NAME OF INTUMESCENT | | | COATING FBC 703.3 | | | |
|