2022-01-10 11:21:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE LVF
 BUT NO FIRE BEHAVIOR RATING FOR THE ACTUAL PROPOSED
 VINYL FLOORING.
  
 VINYL FLOORING IS MANUFACTURED AROUND THE WORLD AND NOT
 ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT
 SPEC SHEETS OF THE PROPOSED FINISHED
 VINYL FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
 2) THERE IS AN INDICATION ON THE APPLICATION OF NEW
 SOUND UNDERLAYMENT BUT NO INDICATION OF THE SPEC SHEET
 FOR THE FLOOR UNDERLAYMENT WITH THE FIRE BEHAVIOR
 RATING.
  
 PLEASE REVIEW AND PROVIDE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  