| Plan Review Notes For Permit 21120936 |
| Permit Number |
21120936 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-19 14:25:53 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | | | | 1.) FBC R 312.3, INDICATE ON DETAIL SHEET THAT THERE | | | WILL BE NO OPENINGS THAT WILL ALLOW PASSAGE OF A 4" | | | DIAMETER SPHERE. | | | 2.) FBC B 1607.8.1.1, DEMONSTRATE THAT THE HANDRAIL AND | | | GUARDS HAVE BEEN DESIGNED TO RESIST A CONCENTRATED LOAD | | | OF 200 POUNDS. | | | 3.) FBC B 107.2.1, PROVIDE ALL DETAILS FOR STRUCTURAL | | | CONNECTIONS INCLUDING FASTENER AND LOAD SPECIFICATIONS. | | | (TYPICALLY THIS IS ACCOMPLISHED BY PROVIDING PRODUCT | | | APPROVALS AND/OR HAVING AN ENGINEER APPROVE THE PLAN) | | | 4.) FBC B R 317.3, FBC R 317.3.1, PROVIDE FASTENER | | | DETAILS/SPECIFICATIONS SHOWING COMPATIBILITY FOR | | | FASTENER CONTACT WITH PRESSURE TREATED LUMBER. | | | |
|