Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-12-22 10:09:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF WHERE THIS PROPOSED
 WALK-IN COOLER IS LOCATED WITHIN THE PROPERTY.
  
 PLEASE PROVIDE A SITE PLAN INDICATING THE SPECIFIC
 LOCATION INCLUDING DIMENSIONS TO OTHER
 BUILDINGS/PROPERTY LINES/SIDEWALKS, STEPUPS/STEPDOWNS
 AT GRADE, ETC.
  
  
  
 2) THERE IS NO INDICATION OF LIGHTING/ELECTRIC TO NOR
 WITHIN THE WALK-IN COOLER.
  
 ELECTICAL WORK SHALL COMPLY WITH NFPA 70, NEC 2017 ED.
  
 PLEASE PROVIDE ELECTICAL DETAILS, INCLUDING HOW AND
 WHERE THE POWER COMES FROM.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  