2022-03-02 15:10:52OUTDOOR COOLER
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THE
 COOLER, THE DISTANCE FROM PROPERTY LINES, THE FLOOD
 ZONE PER THE LATEST FIRM. FBC 107.2.5
  
 2) WIND DESIGN DATA ON THE DRAWINGS AND CALCULATIONS
 SHOWS RISK CATEGORY II WITH WIND SPEED OF 169MPH - THE
 WIND SPEED FOR A RISK CATEGORY II IS 170MPH - PER FBC
 WPB SECTION 120
  