| Plan Review Notes For Permit 21120923 |
| Permit Number |
21120923 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-02 15:10:52 | OUTDOOR COOLER | | | | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THE | | | COOLER, THE DISTANCE FROM PROPERTY LINES, THE FLOOD | | | ZONE PER THE LATEST FIRM. FBC 107.2.5 | | | | | | 2) WIND DESIGN DATA ON THE DRAWINGS AND CALCULATIONS | | | SHOWS RISK CATEGORY II WITH WIND SPEED OF 169MPH - THE | | | WIND SPEED FOR A RISK CATEGORY II IS 170MPH - PER FBC | | | WPB SECTION 120 | | | |
|