Plan Review Notes
Plan Review Notes For Permit 21120917
Permit Number 21120917
Review Stop E
Sequence Number 3
Notes
Date Text
2022-06-13 14:57:481) COMMENT #1 FROM PREVIOUS REVIEW NOT COMPLETELY
 ADDRESSED. THE PRIMARY 100 AMP DISCONNECT FEEDING THE
 50KVA TRANSFORMER IS BEING FED FROM A 150- AMP SOURCE.
 THE RATING OF THIS DISCONNECT REQUIRES A RATING EQUAL
 TO THE SOURCE CURRENT AND VOLTAGE RATING. NEC 110.9
 2) PLEASE PROVIDE CLARITY ON WHICH REQUIREMENTS OF NEC
 240.21 THE SECONDARY CONDUCTORS OF THE 50 KVA
 TRANSFORMER MEET. IT APPEARS THESE CONDUCTORS DETAILED
 DO NOT TERMINATE IN A SINGLE CIRCUIT BREAKER OR THEY
 EXTEND BEYOND THE FIRST DISCONNECTING MEANS.
 3) COMMENT #5 HAS NOT BEEN ADDRESSED. PLEASE PROVIDE
 AVAILABLE SHORT CIRCUIT CALCULATION STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS AT EQUIPMENT TO
 CONFIRM THE STATED AIC RATING OF THE EQUIPMENT AND
 SPD'S IS ADEQUATE. NEC 110.9, 110.10 AND 265.7
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  