| 2022-06-13 14:57:48 | 1) COMMENT #1 FROM PREVIOUS REVIEW NOT COMPLETELY |
| | ADDRESSED. THE PRIMARY 100 AMP DISCONNECT FEEDING THE |
| | 50KVA TRANSFORMER IS BEING FED FROM A 150- AMP SOURCE. |
| | THE RATING OF THIS DISCONNECT REQUIRES A RATING EQUAL |
| | TO THE SOURCE CURRENT AND VOLTAGE RATING. NEC 110.9 |
| | 2) PLEASE PROVIDE CLARITY ON WHICH REQUIREMENTS OF NEC |
| | 240.21 THE SECONDARY CONDUCTORS OF THE 50 KVA |
| | TRANSFORMER MEET. IT APPEARS THESE CONDUCTORS DETAILED |
| | DO NOT TERMINATE IN A SINGLE CIRCUIT BREAKER OR THEY |
| | EXTEND BEYOND THE FIRST DISCONNECTING MEANS. |
| | 3) COMMENT #5 HAS NOT BEEN ADDRESSED. PLEASE PROVIDE |
| | AVAILABLE SHORT CIRCUIT CALCULATION STATING WHAT THE |
| | AVAILABLE SHORT CIRCUIT CURRENT IS AT EQUIPMENT TO |
| | CONFIRM THE STATED AIC RATING OF THE EQUIPMENT AND |
| | SPD'S IS ADEQUATE. NEC 110.9, 110.10 AND 265.7 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |