| 2022-05-06 14:55:14 | ELECTRIC REVIEW FAILED |
| | 1) PLEASE LOCATE ALL EQUIPMENT ON A SITE PLAN. FBC |
| | 107.2 |
| | 2) IT APPEARS THE PRIMARY SIDE DISCONNECT FEEDING THE |
| | 50 KVA TRANSFORMER IS UNFUSED AND THE INCORRECT RATING. |
| | NEC 110.9, 215.3(A) AND 450.3(B)(1) |
| | 3) IT APPEARS THE SECONDARY OF THE 50 KVA TRANSFORMER |
| | IS FEEDING AN ATS WITH NO OVERCURRENT PROTECTION AND IS |
| | THE INCORRECT RATING. NEC 110.9, 215.3 (A) AND |
| | 408.36(B) |
| | 4) PLEASE DETAIL PANELBOARD (A) RATINGS AND OVERCURRENT |
| | PROTECTION FOR BRANCH CIRCUITS.NEC 215.5 AND 240 |
| | 5) PLEASE PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS AT |
| | EQUIPMENT TO CONFIRM THE STATED AIC RATING OF THE |
| | EQUIPMENT AND SPD'S IS ADEQUATE. NEC 110.9, 110.10 AND |
| | 265.7 |
| | 6) PLEASE PROVIDE RATINGS FOR ALL EQUIPMENT NEC 110 , |
| | 285 AND 408 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |
| | |