Plan Review Notes
Plan Review Notes For Permit 21120917
Permit Number 21120917
Review Stop E
Sequence Number 1
Notes
Date Text
2022-01-21 10:52:56ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PLAN SHOWS GENERATOR IS THIS NEW OR EXISTING?
  
 2) PLAN SHOWS 5000 GALLON TANK IS THIS NEW OR EXITING?
  
 3) PLEASE CLARIFY 1 AND 2
  
 4) SUBMIT A SIGNED RISER DIAGRAM FOR SERVICE TO
 EQUIPMENT. 215.5
  
 5) SUBMIT A FAULT CURRENT CALCULATION FOR THE SERVICE
 PER 110.9, 110.10