| Plan Review Notes For Permit 21120917 |
| Permit Number |
21120917 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-21 10:52:56 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) PLAN SHOWS GENERATOR IS THIS NEW OR EXISTING? | | | | | | 2) PLAN SHOWS 5000 GALLON TANK IS THIS NEW OR EXITING? | | | | | | 3) PLEASE CLARIFY 1 AND 2 | | | | | | 4) SUBMIT A SIGNED RISER DIAGRAM FOR SERVICE TO | | | EQUIPMENT. 215.5 | | | | | | 5) SUBMIT A FAULT CURRENT CALCULATION FOR THE SERVICE | | | PER 110.9, 110.10 |
|