| 2022-05-10 17:52:23 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21120914 |
| | 5/10/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. NEW PLANS SUBMITTED. |
| | FLAMINGO PLUMBING HAS SUBMITTED PLANS WHICH CANNOT BE |
| | ACCEPTED FOR FINAL REVIEW WITHOUT SUBMITTAL OF A PERMIT |
| | APPLICATION AS CONTRACTOR OF RECORD- SEC.105.1 WPB, AND |
| | FL. STATUTE 471.025. |
| | |
| | 1) PROVIDE A CIVIL PLAN SHOWING THE WATER SERVICE AND |
| | SANITARY POINTS OF CONNECTION TO MAINS, AND THE |
| | LOCATIONS OF THE WATER METER AND BACKFLOW PREVENTER- |
| | SEC. 107.2.1 WPB. AS NOTED ON THE PLAN A SEPARATE |
| | PERMIT IS REQUIRED FOR THE BACKFLOW PREVENTER- SEC. |
| | 105.1 & 107.2.1 WPB. |
| | |
| | A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A |
| | SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW |
| | PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC. |
| | 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| | TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | 2) P1, P2, P3, P4: THE DRINKING FOUNTAIN DETAIL ON P1 |
| | SHOWS AN OPEN HUB DRAIN WITH A P-TRAP BUT THE ISOMETRIC |
| | SHOWS A DIRECT DRAIN CONNECTION. BASED ON THE CONFLICTS |
| | ON THE PLAN PLEASE PROVIDE PLUMBING PIPING CONNECTION |
| | DETAILS FOR THE DRINKING FOUNTAINS INCLUDING LOCATIONS |
| | OF SHUT OFF VALVES, P-TRAPS AND STUDOR VENTS- SECS. |
| | 606.2, 918.4, 918.5, & 1002.1 FBC P. |
| | |
| | 3) SHEETS P3: PROVIDE A HOSE BIB INSTALLATION DETAIL |
| | SHOWING HOW THE FIXTURES AND THE WATER RISER LINES WILL |
| | BE MOUNTED AND SUPPORTED - SEC. 308.1 FBC P. |
| | |
| | 4) P4: PROVIDE A VENT PIPE RISER DETAIL SHOWING THE |
| | HEIGHT OF THE RISER AND HOW IT WILL BE SUPPORTED AND |
| | PROTECTED FROM DAMAGE- SECS. 305.7 & 308.1 FBC P. |
| | |
| | NEW COMMENT- 5/12/2022: A PLUMBING REVIEW WAS NOT |
| | CONDUCTED UNDER THE MASTER PERMIT-20090914 FOR THE |
| | TENNIS COURTS. PLEASE CONTACT THE ARCHITECT AND/OR |
| | ENGINEER OF RECORD FOR THE COURTS AND PROVIDE PLUMBING |
| | FIXTURE CALCULATIONS FOR THE COURTS IN ACCORDANCE WITH |
| | TABLE 403.1 FBC P. PROVIDE A SCHEDULE THAT INDICATES |
| | THE REQUIRED AND PROVIDED FIXTURES FOR THE OCCUPANCY. |
| | THE ARCHITECT SHALL CLARIFY WHETHER THE COURTS ARE |
| | DESIGNED FOR PUBLIC, PRIVATE, OR BOTH PUBLIC AND |
| | PRIVATE USE, AND ALSO HOW ACCESS TO FIXTURES IS BEING |
| | PROVIDED ONSITE FOR OCCUPANTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |