| Plan Review Notes For Permit 21120898 |
| Permit Number |
21120898 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-05 09:09:46 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 21120898 | | | 1/5/22 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P1.1.1: PLEASE REVISE CIVIL PLANS C3.0 & C3.1 | | | TO SHOW THE CONNECTION POINT OF THE GOLF SHOP SANITARY | | | AND THE MAIN SEWER LINE- SEC. 701.2 FBC P. PLEASE NOTE | | | THAT A BACKWATER VALVE MAY BE REQUIRED- SEC. 714.1 FBC | | | P. | | | | | | 2) P1.1.0 & P7.0.1: VERIFY THAT THE AUTOMATIC WASHING | | | MACHINES WILL DISCHARGE BY GRAVITY INTO THE NEW DRAIN | | | TROUGH- SEC. 406.2 FBC P. | | | | | | 3) P7.03: PROVIDE SHUTOFF VALVES FOR THE WASHING | | | MACHINE SUPPLY LINES- SEC. 606.2 FBC P. | | | | | | 4) P7: PLACE A NOTE TO INDICATE THE ROOF DOWNSPOUTS | | | WILL DISCHARGE AT LEAST 1 FOOT AWAY FROM THE STRUCTURE | | | SIDEWALL, WHETHER BY UNDERGROUND PIPING, TAIL | | | EXTENSIONS, OR SPLASH BLOCKS- SEC. 1503.7 FBC B. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|