| Plan Review Notes For Permit 21120898 |
| Permit Number |
21120898 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-12-30 11:35:54 | REVISION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE APEARANCE OF WALL TILE HAS BEEN REMOVED FROM | | | DRAWING - A9.1.6 DETAIL 9 - PLEASE PROVIDE WALL FINISH | | | DETAIL FBC 1210.2.2 | | | | | | 2) THE APEARANCE OF WALL TILE HAS BEEN REMOVED FROM | | | DRAWING - A9.1.3 DETAIL 3 - PLEASE PROVIDE WALL FINISH | | | DETAIL FBC 1210.2.2 | | | | | | 3) THE APEARANCE OF WALL TILE HAS BEEN REMOVED FROM | | | DRAWING - A9.1.9 DETAIL 7 - PLEASE PROVIDE WALL FINISH | | | DETAIL FBC 1210.2.2 | | | | | | 4) DRAWING A1.1.1B - COOLER DOORS ENCROACH ON THE MEANS | | | OF EGRESS - PLEASE SHOW DIMENSIONS THAT COOLER DOORS | | | WILL COMPLY WITH FBC 1005.7.1 DOORS. | | | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED | | | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY | | | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE | | | THAN ONE-HALF. |
|