Plan Review Notes
Plan Review Notes For Permit 21120881
Permit Number 21120881
Review Stop B
Sequence Number 2
Notes
Date Text
2022-03-07 14:17:46BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 NOTICE: THIS PROPERTY IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA (SFHA). A CONSTRUCTION DRAWING ELEVATION
 CERTIFICATE IS REQUIRED. SEE COMMENTS UNDER THE NFIP
 REVIEW.
  
 1. SEPERATE PRODUCT APPROVALS AND SUBMIT EACH PRODUCT
 APPROVAL AS A SEPERATE PDF. ( *** 2ND REQUEST ***SEE
 WINDOW DOOR NOA DATED 12/27/212, 135 PAGES)
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE THE HOLLOW CORE PLANK SYSTEM DESIGN. ( PLACE
 A DEFERRAL NOTE ON INDEX PGT1)
 SUBMIT HOLLOW CORE PLANK SYSTEM FOR REVIEW PRIOR TO
 INSTALLATION.
  
 3. PROVIDE SHOP DRAWINGS FOR EXTERIOR RAILING SYSTEM.
 (PLACE A DEFERRAL NOTE ON INDEX T1)
 SUBMIT EXT. RAILING SHOP DRAWINGS FOR REVIEW PRIOR TO
 INSTALLATION.
  
 4. CORRECTED
  
 5. CORRECTED
  
 6. GARAGE FINISH FLOOR ELEVATION IS BELOW THE DESIGN
 FLOOD ELEVATION OF 8.0' NAVD. PROVIDE LOCATION OF FLOOD
 OPENINGS.
 IF SMART VENTS ARE UTILIZED, PROVIDE FLORIDA PRODUCT
 APPROVAL NUMBER AND MODEL OF VENT TO BE INSTALLED. ( ON
 FLOOR PLAN A-1 )
  
 NOTE: GARAGE IS 542 SF.
 THREE (3) 8X16 SMART VENTS ARE REQUIRED.
  
 (INSTALL VENTS ON ADJACENT WALLS PER R322.2.2) SEE
 BELOW
  
 R322.2.2.1INSTALLATION OF OPENINGS.
 THE WALLS OF ENCLOSED AREAS SHALL HAVE OPENINGS
 INSTALLED SUCH THAT:
 1. 1.THERE SHALL BE NOT LESS THAN TWO OPENINGS ON
 DIFFERENT SIDES OF EACH ENCLOSED AREA; IF A BUILDING
 HAS MORE THAN ONE ENCLOSED AREA BELOW THE DESIGN FLOOD
 ELEVATION, EACH AREA SHALL HAVE OPENINGS.
 2. 2.THE BOTTOM OF EACH OPENING SHALL BE NOT MORE THAN
 1 FOOT (305 MM) ABOVE THE HIGHER OF THE FINAL INTERIOR
 GRADE OR FLOOR AND THE FINISHED EXTERIOR GRADE
 IMMEDIATELY UNDER EACH OPENING.
 3. 3.OPENINGS SHALL BE PERMITTED TO BE INSTALLED IN
 DOORS AND WINDOWS; DOORS AND WINDOWS WITHOUT INSTALLED
 OPENINGS DO NOT MEET THE REQUIREMENTS OF THIS SECTION.
  
 FEMA TECHNICAL BULLETIN #1
 LOCATION OF FLOOD OPENINGS
 THE IRC AND IBC (BY REFERENCE TO ASCE 24) REQUIRE FLOOD
 OPENINGS ON DIFFERENT SIDES OF EACH ENCLOSED AREA (IRC
 R322.2.2.1) AND IN AT LEAST TWO WALLS OF EACH ENCLOSED
 AREA (ASCE 24, SECTION 2.7.3).
  
 NEW COMMENT:
  
 7. PROVIDE THE FL PRODUCT APPROVAL COVER SHEETS FOR THE
 PROPOSED OHD.
 THE COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE
 VERSION, AND STATUS, FBC R 301.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved