2021-12-30 08:48:561ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21120881
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC
 101.5.1.1.2
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC R403.7.1
  
 3) PLEASE SHOW THE RETURN AIR PATH FROM BEDROOM 1 AND
 BEDROOM 2 TO AHU 2-01. FBC RES M1602.3
  
 4) PLEASE SHOW THE CONDENSATE DRAINAGE LOCATION. FBC
 RES M1411.3
  
 5) SHEET M203: IT APPEARS THAT THE FCU 3-01 IS
 CONDITIONING THE ROOF DECK. PLEASE EXPLAIN. FBC 107.2.1
  
 6) SHEET M201: IT APPEARS THAT THE RETURN FOR THE
 MASTER BEDROOM IS VERY CLOSE TO THE MASTER BATHROOM AND
 THERE DOES NOT APPEAR TO BE A DOOR SEPARATING THE
 MASTER BATH FROM THE MASTER BEDROOM. PLEASE SHOW THAT
 THE RETURN IN THIS AREA MEETS THE REQUIREMENT OF THE
 RETURN AIR CANNOT BE TAKEN FROM A BATHROOM. FBC RES
 M1602.2-4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  