2022-01-10 14:59:04BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: THIS PROPERTY IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA (SFHA). A CONSTRUCTION DRAWING ELEVATION
 CERTIFICATE IS REQUIRED. SEE COMMENTS UNDER THE NFIP
 REVIEW.
  
 1. SEPERATE PRODUCT APPROVALS AND SUBMIT EACH PRODUCT
 APPROVAL AS A SEPERATE PDF.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE THE HOLLOW CORE PLANK SYSTEM DESIGN. THIS
 SHOULD BE REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. PROVIDE SHOP DRAWINGS FOR EXTERIOR RAILING SYSTEM.
 THIS SHOULD BE REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4. PROVIDE AN ENERGY SUBMITTAL.
 R401.2COMPLIANCE.
  
 5. PROVIDE FINISH FLOOR ELEVATION ON FLOOR PLAN AND
 FOUNDATION PLAN. INCLUDE MAIN DWELLING UNIT AND
 ATTACHED GARAGE.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 6. GARAGE FINISH FLOOR ELEVATION IS BELOW THE DESIGN
 FLOOD ELEVATION OF 8.0' NAVD. PROVIDE LOCATION OF FLOOD
 OPENINGS. IF SMART VENTS ARE UTILIZED, PROVIDE FLORIDA
 PRODUCT APPROVAL NUMBER AND MODEL OF VENT TO BE
 INSTALLED.
 NOTE: GARAGE IS 542 SF. THREE (3) 8X16 SMART VENTS ARE
 REQUIRED. INSTALL VENTS ON ADJACENT WALLS.
  
 G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION.
 FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION
 SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO
 THE FOLLOWING:
  
 1) IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY
 WAVE ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS
 TO ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF
 FLOODWATERS.
  
 OPTIONS:
  
 1A) PROVIDE ENGINEERED FLOOD VENTS. DESIGN PROFESSIONAL
 SIGNATURE AND SEAL REQUIRED.
  
 1B) PROVIDE PRODUCT APPROVALS FOR SMART VENTS. INCLUDE
 MODEL OF VENT TO BE INSTALLED.
  
 R322.2.2.1INSTALLATION OF OPENINGS.
 THE WALLS OF ENCLOSED AREAS SHALL HAVE OPENINGS
 INSTALLED SUCH THAT:
 1. 1.THERE SHALL BE NOT LESS THAN TWO OPENINGS ON
 DIFFERENT SIDES OF EACH ENCLOSED AREA; IF A BUILDING
 HAS MORE THAN ONE ENCLOSED AREA BELOW THE DESIGN FLOOD
 ELEVATION, EACH AREA SHALL HAVE OPENINGS.
 2. 2.THE BOTTOM OF EACH OPENING SHALL BE NOT MORE THAN
 1 FOOT (305 MM) ABOVE THE HIGHER OF THE FINAL INTERIOR
 GRADE OR FLOOR AND THE FINISHED EXTERIOR GRADE
 IMMEDIATELY UNDER EACH OPENING.
 3. 3.OPENINGS SHALL BE PERMITTED TO BE INSTALLED IN
 DOORS AND WINDOWS; DOORS AND WINDOWS WITHOUT INSTALLED
 OPENINGS DO NOT MEET THE REQUIREMENTS OF THIS SECTION.
  
 FEMA TECHNICAL BULLETIN #1
 LOCATION OF FLOOD OPENINGS
 THE IRC AND IBC (BY REFERENCE TO ASCE 24) REQUIRE FLOOD
 OPENINGS ?ON DIFFERENT SIDES OF EACH ENCLOSED AREA?
 (IRC R322.2.2.1) AND ?IN AT LEAST TWO WALLS OF EACH
 ENCLOSED AREA? (ASCE 24, SECTION 2.7.3).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  