| Plan Review Notes For Permit 21120866 |
| Permit Number |
21120866 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-07 12:44:58 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 21120866 | | | 1/6/22 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A4.21: SHOW THE CLEAR FLOOR SPACE APPROACH | | | DIAGRAM AND DIMENSIONS AT THE REFRIGERATOR- SECTIONS | | | 305 & 804.6.6 FBC ACC. | | | | | | 2) A4.21: PROVIDE AN ELEVATION DETAIL OR NOTE TO VERIFY | | | THE FREEZER INSIDE THE REFRIGERATOR HAS A MINIMUM OF 50 | | | PERCENT OF FREEZER SPACE 54-INCHES MAXIMUM FROM THE | | | FINISHED FLOOR- SEC. 804.6.6 FBC ACC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|