2022-02-10 08:46:50PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SITE PLAN SHOWING THE EXISTING KITCHEN IS NOT
 LEGIBLE OR CLEAR. SUBMIT CLEAR AND LEGIBLE DIMENSIONED
 FLOOR PLANS SHOWING THE EXISTING KITCHEN WITH CABINET
 AND FIXTURE LOCATIONS AND THE PROPOSED KITCHEN FLOOR
 PLAN. FBC AMENDMENTS 107.2.1
  
 2) PROVIDE A COMPLETE SCOPE OF WORK ON THE PROPOSED
 FLOOR PLAN. FBC AMENDMENTS 107.2.1
  
 3) FBC AMENDMENTS 107.2.1 - INFORMATION ON CONSTRUCTION
 DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 4) IF THIS PROJECT INVOLVES THE REPLACEMENT OR ADDITION
 OF ANY FLOORING, PROVIDE ALL OF THE FOLLOWING THAT
 APPLY:
 -1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC AMENDMENTS
 107.2.1
 -2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 -3. TYPE OF PROPOSED HARD FINISH FLOORING (TILE,
 LAMINATE, WOOD, MARBLE, ETC.).
 -4. STATED VALUE OF WORK.
 -5. DESCRIPTION OF EXISTING SITE CONDITIONS: THICKNESS
 OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW (EXPOSED
 CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL).
 -6. PROPOSED ACOUSTICAL INSULATION UNDERLAYMENT.
 -7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 -8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 -9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
 (UNLESS SUBMITTING ELECTRONICALLY)
 -SUBMIT COPIES OF THE ACTUAL TEST REPORTS FOR THE SOUND
 INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED
 FOR THE APPLICABLE CONSTRUCTION CONDITIONS.
 FBC 603.1 FLAME SPREAD - ASTM E 84-09,
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. PLEASE NOTE
 THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS
 MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  