| Notes |
| Date |
Text |
| 2022-02-10 14:47:52 | ROOFING SYSTEM | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT | | | APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED | | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | | ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE | | | THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-52.5) | | | - SEE NOTE NUMBER 5.7.2 ON THE PRODUCT APPROVAL. | | | |
|