| 2022-01-13 14:20:24 | SIGNATURE REVIEW |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | RE: ELECTRICAL RISER DIAGRAHM |
| | |
| | 1. THE ELECTRICAL CONTRACTOR OR DESIGNER OF RECORD |
| | SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN |
| | SHEETS UNDER THEIR AUTHORITY. |
| | 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, SECTION 107.2.1. |
| | |
| | 2. EITHER UPLOAD DOCUMENTS VIA THE PROJECTDOX PORTAL |
| | WITH SIGNATURE OF CONTRACTOR OR DESIGNER, AS |
| | APPLICABLE; USE THE REQUIRED NAMING CONVENTION FOR EACH |
| | DOCUMENT OR DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH |
| | CONTRACTORS/O/B SIGNATURE TO: |
| | |
| | BUILDING DIVISION, FIRST FLOOR |
| | CITY OF WEST PALM BEACH |
| | 401 CLEMATIS ST |
| | WEST PALM BEACH, FL 33401 |
| | |
| | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. |
| | 481, F.S. & 61G1. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |