| Plan Review Notes For Permit 21120800 |
| Permit Number |
21120800 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-07 15:57:10 | 1) SHEET M2.1 INDICATES THAT VAV 11 IS SUPPLYING 300 | | | CFM TO THE CORRIDOR BUT SHEET M6.1 INDICATES A MAXIMUM | | | OF 200 CFM'S OF SUPPLY AIR FOR VAV-11. PLEASE BE | | | CONSISTENT. | | | | | | 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR THE | | | CORRIDORS. FBC M TABLE 403.3.1.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|