Plan Review Notes
Plan Review Notes For Permit 21120800
Permit Number 21120800
Review Stop B
Sequence Number 1
Notes
Date Text
2022-01-26 14:36:22COMMON AREA BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A0.04 DETAIL 3 SHOWS THE TOILET PAPER HOLDER
 DIMENSION FROM THE FACE OF THE TOILET TO THE CENTER OF
 THE TOILET PAPER HOLDER - PLEASE CORRECT FBC A 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 2) PLEASE SHOW THE CORRIDOR WIDTH FBC TABLE 1020.2
  
 3) PLEASE SHOW THE DIMENSIONS AND THAT DOOR 004 DOES
 NOT ENCROACH THE EGRESS WIDTH MORE THEN ALLOWED FBC
 1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.