Plan Review Notes
Plan Review Notes For Permit 21120704
Permit Number 21120704
Review Stop P
Sequence Number 3
Notes
Date Text
2022-04-07 08:31:363RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21120704
 4/7/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. NO
 NARRATIVE RESPONSE TO PLUMBING COMMENTS WAS PROVIDED AS
 REQUESTED. PLEASE COMPLY
  
 2) FAILED P101 & IN-501: REFER TO SEC. 213.3.1 FBC ACC-
 A MINIMUM OF ONE TOILET COMPARTMENT EACH IN THE MEN'S
 AND WOMEN'S RESTROOMS SHALL COMPLY WITH 604.8.1.
 REQUIRED COMPARTMENT SIZES SHALL 60 INCHES WIDE X 56
 INCHES DEEP FOR WALL HUNG TOILETS. NOT PROVIDED. PLEASE
 SEE SEC. 202.3 FBC ACC FOR FURTHER CLARIFICATION.
  
 3) FAILED ITEMS A, B, C, D, E, F, G, H, I, J. IN-501:
 PROVIDE THE FOLLOWING CORRECTIONS AND MISSING DETAILS
 PER FBC ACC. NOT PROVIDED- SEE BELOW.
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
  
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
  
 C) TURNING SPACE DIAMETERS- SEC. 304.3.
  
 D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.
  
 E) HEIGHTS OF THE MIRRORS MEASURED FROM THE FINISHED
 FLOORS TO THE REFLECTIVE SURFACES- SEC. 603.3.
  
 F) GRAB BAR LENGTHS, AND MOUNTING HEIGHTS OF GRAB BARS
 FOR THE WATER CLOSETS MEASURE FROM THE FINISHED FLOORS
 TO THE TOPS OF THE GRIPPING SURFACES- SECS. 604.5 &
 609.4, FIGURES 604.5.1 & 604.5.2.
  
 G) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
  
 H) HEIGHT AND DEPTH OF THE ACCESSIBLE URINAL- SEC.
 605.2.
  
 I) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 ACCESSIBLE URINAL- SEC. 605.3.
  
 J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
  
 4) FAILED. IN-501: PROVIDE THE WIDTH AND DEPTH
 MEASUREMENTS OF THE STANDARD WATER CLOSETS- SEC.
 405.3.1 FBC P. NOT PROVIDED.
  
 5) FAILED. IN-104: PAINTED DRYWALL SURROUNDING THE MOP
 SINK IS NOT AN APPROVED MATERIAL FOR WALL FINISH. REFER
 TO SECTION 310.3 FBC P AND SECTION 1210.2.2 FBC B WALLS
 AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. NOT
 PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy