Plan Review Notes
Plan Review Notes For Permit 21120704
Permit Number 21120704
Review Stop P
Sequence Number 2
Notes
Date Text
2022-02-10 09:09:442ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21120704
 2/10/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS AD101 & P101: THE PLANS SHOW RELOCATION OF
 LAVATORIES IN THE MEN'S RR 102. PLEASE PROVIDE PLUMBING
 RISER DRAWINGS- SEC. 107.3.5.1.3 WPB.
  
 2) P101 & IN-501: REFER TO SEC. 213.3.1 FBC ACC- A
 MINIMUM OF ONE TOILET COMPARTMENT EACH IN THE MEN'S AND
 WOMEN'S RESTROOMS SHALL COMPLY WITH 604.8.1. REQUIRED
 COMPARTMENT SIZES SHALL 60 INCHES WIDE X 56 INCHES DEEP
 FOR WALL HUNG TOILETS.
  
 3) IN-501: PROVIDE THE FOLLOWING CORRECTIONS AND
 MISSING DETAILS PER FBC ACC.
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
  
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
  
 C) TURNING SPACE DIAMETERS- SEC. 304.3.
  
 D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.
  
 E) HEIGHTS OF THE MIRRORS MEASURED FROM THE FINISHED
 FLOORS TO THE REFLECTIVE SURFACES- SEC. 603.3.
  
 F) GRAB BAR LENGTHS, AND MOUNTING HEIGHTS OF GRAB BARS
 FOR THE WATER CLOSETS MEASURE FROM THE FINISHED FLOORS
 TO THE TOPS OF THE GRIPPING SURFACES- SECS. 604.5 &
 609.4, FIGURES 604.5.1 & 604.5.2.
  
 G) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
  
 H) HEIGHT AND DEPTH OF THE ACCESSIBLE URINAL- SEC.
 605.2.
  
 I) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 ACCESSIBLE URINAL- SEC. 605.3.
  
 J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
  
 4) IN-501: PROVIDE THE WIDTH AND DEPTH MEASUREMENTS OF
 THE STANDARD WATER CLOSETS- SEC. 405.3.1 FBC P.
  
 5) IN-104: PAINTED DRYWALL SURROUNDING THE MOP SINK IS
 NOT AN APPROVED MATERIAL FOR WALL FINISH. REFER TO
 SECTION 310.3 FBC P AND SECTION 1210.2.2 FBC B WALLS
 AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@
  