Plan Review Notes
Plan Review Notes For Permit 21120704
Permit Number 21120704
Review Stop B
Sequence Number 1
Notes
Date Text
2022-01-04 11:32:07WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21120704
 ADD: 777 S. FLAGLER DR. # 18TH FFLOOR/ COMMON AREAS
 CONT: TBD/ TO BE DETERMINED
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 04/2022
 ACTION: DENIED
  
 1) THE SUBMITTED PERMIT APPLICATION IS EXTREMELY LOW
 FOR THE WORK SHOWN ON THE PLANS. MAY NOT EVEN COVER THE
 DESIGN FEES.
 109.3 BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, CANOPIES, ALL LOW VOLTAGE PERMITS, GENERATORS
 & FUEL TANKS WITH FILL STATIONS, GAS PERMIT, POOL,
 JACUZZI AND ASSOCIATED SUB-PERMITS, AWNING, SCREEN
 ENCLOSURES, CANOPY, FENCE, LANDSCAPE, IRRIGATION, AUGER
 CAST PILE AND OR FOUNDATION OR STRUCTURE ONLY PERMIT
 WILL BE SEPARATE REVIEWS AND ASSOCIATED FEES WITH EACH
 PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 2) SHEET G001 ACCESSIBILITY STANDARDS:
 2A) GRAB BARS/ RESTROOMS> 2020 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 2B) TISSUE DISPENSER, ( R ) (B ) THE WRITTEN WORDS
 INDICATES THE TISSUE DISPENSER TO BE WITHIN 12 INCHES
 OF THE FRONT OF THE TOILET SEAT. TOILET PAPER
 DISPENSERS. 604.7. THE TOILET PAPER DISPENSER SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM TO 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 THE OUTLET OF THE DISPENSER SHALL BE 15 INCHES MINIMUM
 AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL
 NOT BE LOCATED BEHIND THE GRAB BARS.
  
 3) LIFE SAFETY SHEET
 3A) LIFE SAFETY NOTES, NOTE A INDICATES THIS BUILDING
 TYPE AS TYPE II-B, FULLY SPRINKLERED. UNDER THE HEADING
 OF PROJECT DATA, THE INTERIOR SPACE TO BE RENOVATED IS
 THE 18TH FLOOR COMMON AREAS. PLEASE REFER TO THE 2020
 FBC-BUILDING CODE TABLE 504.4 TYPE II-B CONSTRUCTION /
 SPRINKLERED FOR A BUSINESS OCCUPANCY ONLY ALLOWS A
 4-STORY BUILDING. 18 STORIES REQUIRE BUILDING TYPE IA
 (UNLIMITED).
  
 3B) SHEET AD101 THE 18TH FLOOR DEMOLITION PLAN SHOWS A
 NOTE # 2 THE REMOVAL OF ELEVATOR LOBBY DOORS. THE LIFE
 SAFETY PLAN DOES NOT SHOW THE ELEVATOR DOORS BEING
 REPLACED. THE LIFE SAFETY PLAN WILL NEED TO SHOW HOW
 COMPLIANCE WITH SECTION 3006.3 HOISTWAY OPENING
 PROTECTION. PLEASE PROVIDE COMPLIANCE WITH ONE OF THE
 FOUR OPTIONS THE BUILDING CODE GIVES.
 THE 2020 EXISTING BUILDING CODE SECTION 803.2.2 TRIES
 TO ADDRESS THIS SECTION BUT IT IS WHEN THE WORK AREA
 EXCEEDS 50% OF THE FLOOR AREA. THIS HAS OCCURRED WITH
 THE DEMOLITION PERMIT 21100011 ISSUED 11/29/21.
 PLEASE ALSO REFER TO 2020 EXISTING BUILDING CODE. 801.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4A) SHEET IN801 MATERIAL FINISHES DOES NOT ADDRESS WALL
 SURFACES AT SERVICE SINKS, URINALS, AND WATER CLOSETS
 AND COMPLIANCE WITH 2020 FBC-B 1210.2.2. WALLS &
 PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING
 OFFICIAL INTERPRETATION ON 06/2020. IN BATHROOMS,
 RESTROOMS & SERVICE SINK AREAS EPOXY PAINT IS NO LONGER
 CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 4B) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  