| 2021-12-20 07:32:05 | 1) PLEASE SUBMIT THE MECHANICAL DRAWINGS SHOWING THE | | | TIE DOWNS OF THE CONDENSING UNITS. FBC 107.2.1 | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING FOR | | | EACH MECHNAICAL UNIT INSTALLED. FBC EC C403.2.1 | | | | | | 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS | | | USE OF SPACE FOR EACH UNIT. FBC M 403.3.1.1 AND TABLE | | | 403.3.1.1 | | | | | | 4) PLEASE SHOW THE CONDENSATION PIPING, MATERIAL, SIZE | | | AND TERMINATION LOCATION. FBC M 307 | | | | | | 5) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS USE | | | OF SPACE. FBC EC C402 | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|