Plan Review Notes
Plan Review Notes For Permit 21120607
Permit Number 21120607
Review Stop M
Sequence Number 4
Notes
Date Text
2022-04-26 17:10:511ST REVIEW FMC
 PERMIT: 21120607
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RESPONSE LETTER REFERENCED IN THE RESUBMITTAL
 LETTER WAS NOT INCLUDED. THERE IS A NOTE ON SHEET M02
 THAT STATES THE ROOM WILL NOT HAVE MORE THAN 63
 OCCUPANTS IN ACCORDANCE WITH THE OWNER?S DESIGN
 REQUIREMENTS AND STATISTICAL DATA. THE STATISTICAL DATA
 WILL NEED TO BE INCLUDED IN THE RESUBMITTAL FOR REVIEW.
 SEE EXCEPTION BELOW
  
 403.3.1.1 EXCEPTION: THE OCCUPANT LOAD IS NOT REQUIRED
 TO BE DETERMINED BASED ON THE ESTIMATED MAXIMUM
 OCCUPANT LOAD RATE INDICATED IN TABLE 403.3.1.1 WHERE
 APPROVED STATISTICAL DATA DOCUMENT THE ACCURACY OF
 AN ALTERNATE ANTICIPATED OCCUPANT DENSITY.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  