| Date |
Text |
| 2022-03-02 14:31:17 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 21120607 |
| | 2/16/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED IST AND 2ND REVIEW |
| | COMMENTS LISTED BELOW. |
| | |
| | 1) 2ND REQUEST- FAILED. SHEET A-3.1: THE PLUMBING |
| | FIXTURE CALCULATIONS DO NOT INCLUDE THE REQUIRED |
| | SERVICE SINKS AND DRINKING FOUNTAINS, AND THEIR |
| | LOCATIONS ARE NOT SHOWN ON THE PLANS- TABLE 403.1 FBC |
| | P. PLEASE REVISE THE PLANS TO INCLUDE THE REQUIRED |
| | FIXTURES. THE CALCULATIONS FOR A3 SHOWN ON THE PLAN ARE |
| | INCORRECT. FEMALE WATER CLOSETS ARE CALCULATED AT 1 PER |
| | 75 FOR CHURCHES- TABLE 403.1 FBC P. THE 2ND REQUIRED |
| | FEMALE WATER CLOSET PREVIOUSLY SHOWN IN THE |
| | CALCULATIONS WAS REMOVED FROM THE RESUBMITTED PLAN. |
| | |
| | 3) 2ND REQUEST- FAILED SHEET A-7.4 ITEMS C, D, & E. |
| | A-7.4: |
| | C) FAILED. HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER |
| | SURFACES FROM THE FINISHED FLOORS- 606.3. NOT PROVIDED. |
| | D) FAILED. HEIGHTS OF THE MIRRORS FROM THE FINISHED |
| | FLOORS TO THE REFLECTIVE SURFACES- SEC. 603.3. THE |
| | MEASUREMENT SHOWN IS TO THE MIRROR FRAME, NOT THE |
| | REFLECTIVE SURFACE. |
| | E) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| | GRAB BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. PLEASE NOTE THE 2'11" |
| | MEASUREMENT IN ELEV. 3 IS SHOWN TO THE CENTER OF THE |
| | GRAB BAR AND NOT TO THE TOP OF THE GRIPPING SURFACE. |
| | NOTE- THE GRAB BARS LISTED IN THE SCHEDULE DO NOT MATCH |
| | THE GRAB BARS IN THE DRAWINGS. PLEASE SEE FIGURES |
| | 604.5.1 & 604.5.2 FBC ACC: SHOW THE 12-INCH MAX SPACING |
| | AND MIN. 54-INCH EXTENSION FOR THE SIDE GRAB BAR, AND |
| | SHOW THE REAR GRAB BAR WILL EXTEND MIN. 12-INCHES ONE |
| | WAY FROM THE CENTERLINE OF THE WATER CLOSET, AND MIN. |
| | 24-INCHES FROM THE CENTERLINE TO THE OPEN SIDE. |
| | |
| | 4) 2ND REQUEST FAILED SHEET A7.4- ITEMS A, C, D, E, F, |
| | & H: PLEASE PROVIDE AN ENLARGED DRAWING OF THE PRIEST |
| | OFFICE BATHROOM WITH FIXTURE AND ACCESSORY ELEVATION |
| | DETAILS. PLEASE NOTE THAT PRIVATE BATHROOMS CONSTRUCTED |
| | UNDER THE FBC ACC SHALL BE IN COMPLIANCE WITH THE |
| | FOLLOWING CODE SECTIONS: |
| | A) FAILED. CLEAR FLOOR SPACES FOR WATER CLOSETS- SEC. |
| | 604.3. MINIMUM 56-INCHES DEEP X 60-INCHES WIDE SPACE |
| | REQUIRED. |
| | B) FAILED. CLEAR FLOOR SPACES FOR LAVATORIES- SEC. |
| | 606.2. THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR |
| | SPACE- SEC. 603.2.3. |
| | C) FAILED. CENTERLINE OF THE WATER CLOSET FROM THE SIDE |
| | WALL- SEC.604.2. THE WATER CLOSET IS NOT POSITIONED AT |
| | THE SIDE WALL. |
| | D) FAILED. HEIGHT OF MIRROR FROM FINISHED FLOOR TO |
| | REFLECTIVE SURFACE- SEC. 603.3. ELEVATION DETAIL DOES |
| | NOT PROVIDE A MEASUREMENT. |
| | E) FAILED. REINFORCEMENT LOCATIONS FOR FUTURE GRAB BARS |
| | AT WATER CLOSETS- SEC. 604.5 EXCEPTION 1. WATER CLOSET |
| | NOT POSITIONED FOR A FUTURE SIDE WALL GRAB BAR TO BE |
| | PROVIDED |
| | F) FAILED. SHOWER TYPE, SHOWER DIMENSIONS, CLEAR FLOOR |
| | SPACE FOR SHOWER, CONTROLS LOCATIONS, AND REINFORCEMENT |
| | LOCATIONS FOR FUTURE GRAB BARS- SECS. 608.1- 608.7. THE |
| | SHOWER IS NOT SET UP FOR ACCESSIBLE USE ACCORDING TO |
| | SECS- 608.1- 608.7 |
| | H) FAILED. CENTERLINE OF THE TOILET PAPER DISPENSER |
| | MEASURED FROM THE FRONT OF THE WATER CLOSET- SEC. AND |
| | FIGURE 604.7. WATER CLOSET AND TP DISPENSER NOT |
| | POSITIONED AT SIDE WALL. |
| | |
| | 13) 2ND REQUEST- FAILED SHEET P0.1: PROVIDE SHOWER PAN |
| | DRAIN, LINER, AND WALL FINISH DETAILS- SECS. 417.3, |
| | 417.4.1, & 417.5.2 FBC P. NOT PROVIDED. PLEASE NOTE |
| | THAT THE 3'-4" CERAMIC WALL HEIGHTS SHOWN ON SHEET A7.4 |
| | ARE NOT IN COMPLIANCE WITH SEC. 1210.2.2 FBC B WHICH |
| | REQUIRES THE TILE TO BE 4FT. IN HEIGHT AT THE WATER |
| | CLOSETS. |
| | |
| | NEW COMMENT |
| | 1) SHEETS P0.1 & P0.2: REFER TO SEC. 607.1.1 FBC P AND |
| | PROVIDE EITHER A MASTER THERMOSTATIC MIXING VALVE AT |
| | THE WATER HEATER OR INDIVIDUAL MIXING VALVES AT |
| | FIXTURES SUPPLYING HOT WATER INCLUDING THE HAND SINKS, |
| | MOP SINKS, AND 3-COMPARTMENT SINKS. PLEASE NOTE THE |
| | LAVATORY SINKS ARE APPROVED FOR DELIVERY OF TEMPERED |
| | WATER USING THE ASSE 1070 MIXING VALVES. |
| | |
| | 2) DRINKING FOUNTAINS: REFER TO SECTIONS 306, 307, AND |
| | 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN INSTALLATION |
| | DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE |
| | CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW |
| | THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A |
| | FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION |
| | 602.2 FBC ACC, AND SHOW HOW THE LOCATIONS OF THE |
| | FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2 |
| | PROTRUSION LIMITS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |