Plan Review Notes
Plan Review Notes For Permit 21120607
Permit Number 21120607
Review Stop M
Sequence Number 3
Notes
Date Text
2022-03-10 08:37:31SHEET M1.1 INDICATES THAT THE OAF-1 IS INTRODUCING 1000
 CFM'S OF OUTDOOR AIR TO THE SOCIAL HALL. FBC M SECTION
 403.3.1.1 TELLS US THAT WE MUST USE TABLE 403.3.1.1 TO
 DETERMINE HOW MUCH OUTDOOR AIR IS REQUIRED FOR EACH USE
 OF SPACE, BASED ON THE SQURE FOOTAGE AND THE USE OF
 SPACE IS A MULTI-USE ASSEMBLY THE REQUIRED OUTDOOR AIR
 WILL BE 1,514 CFM'S. UNLESS THE ENGINEER DESIGNS A
 SYSTEM BASED ON THE EXCEPTION OF FBC M 403.2 THE
 OUTDOOR AIR REQUIRED WILL BE 1,514 CFM'S FOR THIS
 SPACE.
  
  