| 2022-03-10 08:37:31 | SHEET M1.1 INDICATES THAT THE OAF-1 IS INTRODUCING 1000 | | | CFM'S OF OUTDOOR AIR TO THE SOCIAL HALL. FBC M SECTION | | | 403.3.1.1 TELLS US THAT WE MUST USE TABLE 403.3.1.1 TO | | | DETERMINE HOW MUCH OUTDOOR AIR IS REQUIRED FOR EACH USE | | | OF SPACE, BASED ON THE SQURE FOOTAGE AND THE USE OF | | | SPACE IS A MULTI-USE ASSEMBLY THE REQUIRED OUTDOOR AIR | | | WILL BE 1,514 CFM'S. UNLESS THE ENGINEER DESIGNS A | | | SYSTEM BASED ON THE EXCEPTION OF FBC M 403.2 THE | | | OUTDOOR AIR REQUIRED WILL BE 1,514 CFM'S FOR THIS | | | SPACE. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | |
|