Plan Review Notes
Plan Review Notes For Permit 21120607
Permit Number 21120607
Review Stop M
Sequence Number 2
Notes
Date Text
2022-02-22 17:17:15YOUR RESPONSE FOR PREVIOUS COMMENT 5 BELOW DOES NOT
 MAKE SENSE AS THE SHEET REFERENCED IN YOUR COMMENT DOES
 NOT EXIST IN THIS PACKAGE AND THERE ARE SEVERAL UNITS
 CONDITIONING THE SOCIAL HALL, SOME ARE NOT LISTED IN
 YOUR RESPONSE.
  
 5) SHEET M11 DETAIL 5 SHEET M1.3 IS NOT IN THIS
 PACKAGE. PLEASE PROVIDE A DETAIL OF HOW THE OUTDOOR AIR
 WILL BE CONDITIONED BEFORE IT ENTERS THE SPACE. FBC
 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER