| 2022-02-08 10:22:31 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 21120607 |
| | W. P. B. PERMIT: 20120918 |
| | ADD: 509 21ST. STREET |
| | CONT: PATTERSON CONSTRUCTION |
| | TEL: 561-437-3059 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. DEC. 21/2021 |
| | ACTION: FAILED |
| | |
| | 1) 2ND REQUEST. !!!!!!!!!THE REVISION 21120607 DOES NOT |
| | SHOW A INCREASE IN VALUE ALL TOUGH THE PLANS CLEARLY |
| | SHOW A SUBSTANIAL INCREASE IN THE SCOPE OF WORK. |
| | INCLUDE ROOF VALUE OR STATE THAT THE ROOFING PERMIT IS |
| | TO HAVE THE FEES PAID UNDER THE ROOF PERMIT. |
| | 109.3 BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2-3) COMPLIED. |
| | 4) THE SHEET A-2.2, A-3.3 VS A3.4, CHOIR LOFT. |
| | |
| | 4A) SEMI-COMPLIED. THIS REVIEW CYCLE THE DOOR ROUGH |
| | OPENING IS GIVEN FOR THE MASONRY OPENING, PLEASE |
| | PROVIDE THE CLEAR WIDTH DOOR OPENING WITH THE DOOR |
| | OPENED AT 90 DEGREES. 2017 FBC-B 1010.1.1 AND TABLE |
| | 716.5 OPENING PROTECTIVES. |
| | CHOIR |
| | 1ST ROUND OF COMMENTS. THE DOORS LEADING THE STAIRWAY |
| | VERTICAL SHAFT DO NOT GIVE ANY SIZE NOR FIRE RATING. |
| | 2017 FBC-B 1010.1.1 AND TABLE 716.5 OPENING |
| | PROTECTIVES. |
| | |
| | 4B) 2ND ROUND OF COMMENTS. SHEET A-3.4 IS LABELED THE |
| | FIRST FLOOR LIFE SAFETY PLAN WHEREAS UPLOADED THE |
| | ACTUAL PLAN IS A 2ND BASEMENT PLAN LOADED TWICE. |
| | PROVIDE THE OCCUPANT LOAD FOR THE CHOIR LOFT. PLEASE |
| | REVIEW 1011.10 OF THE FLORIDA BUILDING CODE SECTION |
| | 1011.10 WHERE SPIRAL STARS IN A COMMERCIAL APPLICATION |
| | CAN ONLY BE USED WHEN IN USE FOR A TECHNICAL PRODUCTION |
| | AREAS IN ACCORDANCE WITH 410.6.SECTION 410.6 .3.1 NO |
| | FEWER THAN ONE MEANS OF EGRESS SHALL BE PROVIDED FROM |
| | TECHNICAL PRODUCTION AREAS. |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST ROUND OF COMMENTS. THE COVERSHEET NOR ANY LIFE |
| | SAFETY SHEET GIVE THE OCCUPANT LOAD OF THE CHOIR LOFT, |
| | THIS IS NEEDED TO DETERMINE THE OCCUPANT LOAD TO USE |
| | THE STAIR TO THE CHOIR LOFT. 107.2.1.2. ADDITIONAL |
| | INFORMATION REQUIRED. PLEASE SHOW COMPLIANCE FOR |
| | 1011.10 SPIRAL STAIRWAY AND AN OCCUPANT LOAD OF NOT |
| | MORE THAN 5 OCCUPNTS. |
| | |
| | 4C) IF THE SPIRAL STAIRCASE CAN BE CONSIDERED A MEANS |
| | OF EGRESS PLEASE PROVIDE SHOP DRAWINGS IN COMPLIANCE |
| | WITH 1011. 10 & 1011.11. |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |