Plan Review Notes
Plan Review Notes For Permit 21120607
Permit Number 21120607
Review Stop P
Sequence Number 1
Notes
Date Text
2021-12-30 11:05:281ST REVIEW FBC-2017 PLUMBING
 PERMIT- 21120607
 12/30/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-3.1: THE PLUMBING FIXTURE CALCULATIONS DO
 NOT INCLUDE THE REQUIRED SERVICE SINKS AND DRINKING
 FOUNTAINS, AND THEIR LOCATIONS ARE NOT SHOWN ON THE
 PLANS- TABLE 403.1 FBC P. PLEASE REVISE THE PLANS TO
 INCLUDE THE REQUIRED FIXTURES.
  
 2) SHEET A3.1 & A-3.3: LABEL THE TOILETS ROOMS AS MALE,
 FEMALE, FAMILY, OR ASSISTED USE IN ACCORDANCE WITH
 SECS. 403.1.2 & 403.2 FBC P. PLEASE REMOVE THE
 "EXISTING TOILET ROOM TO REMAIN" NOTES. THE DEMOLITION,
 ARCHITECTURAL AND PLUMBING PLANS INDICATE NEW TOILET
 ROOMS- SEC. 107.2.1 WPB.
  
 3) A-7.4: PLEASE INDICATE WHICH CODE IS BEING USED TO
 DESIGN THE MEN'S AND WOMEN'S HANDICAP BATHROOMS. ADA IS
 NOTED IN THE DETAILS HOWEVER SHEET A-3.3 INDICATES THE
 PLANS HAVE BEEN DESIGNED IN ACCORDANCE WITH FLORIDA
 BUILDING CODE- 2017. THE FBC-17 INCLUDES FLORIDA
 ACCESSIBILITY CODE- 2017. PLEASE REVIEW SEE THE LIST OF
 FBC ACC COMPLIANCES BELOW AND REVISE THE PLAN:
 A) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS
 SHALL BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM- SEC.
 604.2. THE PLAN SHOWS 19-1/2-INCHES.
 B) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS SHALL 17 INCHES MINIMUM AND 19 INCHES MAXIMUM TO
 THE TOP OF THE SEAT- 604.4.
 C) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOORS- 606.3.
 D) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. PLEASE NOTE THE 2'11"
 MEASUREMENT IN ELEV. 3 IS SHOWN TO THE CENTER OF THE
 GRAB BAR AND NOT TO THE TOP OF THE GRIPPING SURFACE.
 NOTE- THE GRAB BARS LISTED IN THE SCHEDULE DO NOT MATCH
 THE GRAB BARS IN THE DRAWINGS.
 F) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS SHALL
 BE ON THE OPEN SIDES OF THE WATER CLOSETS, NOT ON THE
 CLOSED SIDES- 604.6.
 G) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
 H) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2 AND FIGURES 306.2 & 306.3.
 I) REACH HANDLE HEIGHTS OF THE DIAPER CHANGING STATIONS
 IN THE CLOSED POSITIONS, AND THE HAND TOWEL DISPENSERS
 (NOTE- DISPENSER LOCATIONS NOT SHOWN IN THE DRAWINGS)-
 SEC. 308.
  
 4) A-7.4: PLEASE PROVIDE AN ENLARGED DRAWING OF THE
 PRIEST OFFICE BATHROOM WITH FIXTURE AND ACCESSORY
 ELEVATION DETAILS. PLEASE NOTE THAT PRIVATE BATHROOMS
 CONSTRUCTED UNDER THE FBC ACC SHALL BE IN COMPLIANCE
 WITH THE FOLLOWING CODE SECTIONS:
 A) CLEAR FLOOR SPACES FOR WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACES FOR LAVATORIES- SEC. 606.2.
 C) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SEC.604.2.
 D) HEIGHT OF MIRROR FROM FINISHED FLOOR TO REFLECTIVE
 SURFACE- SEC. 603.3
 E) REINFORCEMENT LOCATIONS FOR FUTURE GRAB BARS AT
 WATER CLOSETS- SEC. 604.5 EXCEPTION 1.
 F) SHOWER TYPE, SHOWER DIMENSIONS, CLEAR FLOOR SPACE
 FOR SHOWER, CONTROLS LOCATIONS, AND REINFORCEMENT
 LOCATIONS FOR FUTURE GRAB BARS- SECS. 608.1- 608.7.
 G) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SEC.
 604.6.
 H) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONT OF THE WATER CLOSET- SEC. AND FIGURE
 604.7.
  
 5) A-7.4: IN STANDARD TOILET ROOMS THE WATER CLOSET AND
 VANITY SHALL NOT BE CLOSER THAN 30 INCHES CENTER TO
 CENTER- SEC. 405.3.1 FBC P. THE UNISEX PLAN SHOWS 28
 INCHES.
  
 6) P0.1, P0.2, & P1.1: SINKS AND DISHWASHERS IN FOOD
 PREP AREAS SHALL DISCHARGE THROUGH AN INDIRECT WASTE
 PIPE INTO APPROVED WASTE RECEPTORS- SECS. 802.1,
 802.1.1, 802.1.6, 802.1.7, 802.2, AND 802.3 FBC P.
 PLEASE REVISE THE PLANS ACCORDINGLY.
  
 7) P0.1, P0.2, & P1.1: A GREASE INTERCEPTOR IS REQUIRED
 TO RECEIVE THE DRAINAGE FROM THE SINK AND DISHWASHER IN
 THE FOOD PREP AREAS- SEC. 1003.3.1 FBC P. INSTALLATION
 OF THE INTERCEPTOR SHALL BE UNDER SEPARATE PERMIT- SEC.
 105.1 WPB.
 A) REVISE THE PLANS TO SHOW THE LOCATION OF THE
 INTERCEPTOR AND PLUMBING PIPING REQUIREMENTS. SHOW THE
 GREASE WASTE PIPING RUNS FROM THE FIXTURES TO THE
 INTERCEPTOR AND FROM THE INTERCEPTOR TO POINT OF
 CONNECTION TO THE EXISTING BUILDING OR SEWER DRAIN.
 SHOW LOCATIONS OF ALL REQUIRED CLEANOUTS AND VENTS PER
 MANUFACTURER'S SPECIFICATIONS- SECTION 1003.3.4 FBC P
 AND SECTION 107.2.1 WPB.
 B) PROVIDE GREASE WASTE CALCULATIONS AND INTERCEPTOR
 EQUIPMENT SCHEDULE ON THE PLAN IN COMPLIANCE WITH
 SECTION 1003.3.5 FBC P.
  
 8) P0.1: PLEASE INCLUDE THE TOILET ROOM, BATHROOM, FOOD
 PREP, AND SACRISTY FIXTURES AND FAUCETS IN THE
 SCHEDULE- SEC. 107.2.1 WPB AND TABLE 604.5 FBC P.
  
 9) P0.1: PLEASE INCLUDE THE EFFICIENCY RATING OF THE
 WATER HEATER IN THE SCHEDULE- TABLE C404.2 FBC EC.
  
 10) P0.1, P1.0 & P1.1: SHOW THE WATER HEATER PAN DRAIN
 LINE RUN TO DISCHARGE LOCATION- SEC. 504.7.2 FBC P.
  
 11) P1.0 & P1.1: THE 1/2-INCH HOT WATER SUPPLY PIPES TO
 THE LAVATORIES ARE EXCEEDING THE MAXIMUM 2 FT. LENGTHS
 ALLOWED FROM THE NEAREST HOT WATER SOURCE TO THE
 FIXTURE SUPPLY PIPE TERMINATION POINT- SEC. C404.5.1
 FBC EC. EITHER PROVIDE RECIRCULATION LOOPS AT THE
 LAVATORIES OR POINT OF USE WATER HEATERS.
  
 12) P0.1, P1.0, & P1.1: INDICATE HOW TEMPERED WATER
 WILL BE DELIVERED FROM THE LAVATORIES- SEC. 416.5 FBC
 P.
  
 13) P0.1: PROVIDE SHOWER PAN DRAIN, LINER, AND WALL
 FINSIH DETAILS- SECS. 417.3, 417.4.1, & 417.5.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  