2021-12-20 17:10:201ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21120607
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.2: IN THE VENTILATION CALCULATIONS, PLEASE
 REFERENCE THE 2020 FBC MECHANICAL CODE. THE ASHRAE
 170-2017 IS FOR HEALTH CARE FACILITIES, PLEASE EXPLAIN
 HOW THIS APPLIES TO THIS OCCUPANCY.
  
 2) SHEET M0.2: VENTILATION CALCULATIONS: THE MEETING
 ROOM APPEARS TO BE CALCULATED AS A CONFERENCE ROOM,
 THIS AREA SHOULD BE CALCULATED AS A MULTIUSE ASSEMBLY.
 FBC M TABLE 403.3.1.1
  
 3) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C403.2.1
  
 4) PLEASE MAKE SURE ALL OUTDOOR AIR INTAKES ARE 10 FEET
 FROM EXHAUST TERMINATIONS. FBC M 401.4-2
  
 5) SHEET M11 DETAIL 5 SHEET M1.3 IS NOT IN THIS
 PACKAGE. PLEASE PROVIDE A DETAIL OF HOW THE OUTDOOR AIR
 WILL BE CONDITIONED BEFORE IT ENTERS THE SPACE. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  