| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M0.2: IN THE VENTILATION CALCULATIONS, PLEASE |
| | REFERENCE THE 2020 FBC MECHANICAL CODE. THE ASHRAE |
| | 170-2017 IS FOR HEALTH CARE FACILITIES, PLEASE EXPLAIN |
| | HOW THIS APPLIES TO THIS OCCUPANCY. |
| | |
| | 2) SHEET M0.2: VENTILATION CALCULATIONS: THE MEETING |
| | ROOM APPEARS TO BE CALCULATED AS A CONFERENCE ROOM, |
| | THIS AREA SHOULD BE CALCULATED AS A MULTIUSE ASSEMBLY. |
| | FBC M TABLE 403.3.1.1 |
| | |
| | 3) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FBC EC C403.2.1 |
| | |
| | 4) PLEASE MAKE SURE ALL OUTDOOR AIR INTAKES ARE 10 FEET |
| | FROM EXHAUST TERMINATIONS. FBC M 401.4-2 |
| | |
| | 5) SHEET M11 DETAIL 5 SHEET M1.3 IS NOT IN THIS |
| | PACKAGE. PLEASE PROVIDE A DETAIL OF HOW THE OUTDOOR AIR |
| | WILL BE CONDITIONED BEFORE IT ENTERS THE SPACE. FBC |
| | 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |