| 2021-12-21 09:13:23 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 21120607 |
| | W. P. B. PERMIT: 20120918 |
| | ADD: 509 21ST. STREET |
| | CONT: PATTERSON CONSTRUCTION |
| | TEL: 561-437-3059 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. DEC. 21/2021 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) THE REVISION 21120607 DOES NOT SHOW A INCREASE IN |
| | VALUE ALL TOUGH THE PLANS CLEARLY SHOW A SUBSTANIAL |
| | INCREASE IN THE SCOPE OF WORK. |
| | 109.3 BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) SHEET A-3.1 & A-3.2 BOTH SHOW A NEW VERTICAL |
| | PLATFORM LIFT. THE FLOOR PLAN DOES NOT PROVIDE A |
| | DETAIL/ SECTION OF THE VERTICAL SHAFT NOR THE HOUR |
| | RATING OF HE SHAFT NOR RATING OF THE OPENING |
| | PROTECTIVES ( FIRE RATED DOORS). 2017 FBC-BUILDING CODE |
| | SECTIONS 707.3.1 SHAFT CONSTRUCTION, 3002.1 HOISTWAY |
| | ENCLOSURE PROTECTION AND OPENING PROTECTION TABLE |
| | 716.5. |
| | |
| | 3) THE PLAN STATES A PLATFORM LIFT, PLATFORM LIFTS NEED |
| | TO SHOW COMPLIANCE WITH SECTION 410 OF THE 2017 ACCESS. |
| | CODE. DOES THE DESIGNER OF RECORD MEAN A LULA LIFT IN |
| | ACCORDANCE WITH 408 OF THE 2017 ACCESSIBILITY CODE. |
| | PLEASE PROVIDE DETAILS, SECTIONS AND THE APPROPRIATE |
| | LITERATURE FOR THE TYPE OF LIFT TO BE INSTALLED. |
| | 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4) THE SHEET A-2.2 DATED 2/10/2021 SHOWER STAIRS TO |
| | CHOIR LOFT TO BE DEMOLISHED, WOOD PLATFORM FRAME OVER |
| | EXISTING METAL POST TO REMAIN, THIS WAS THE SHEET THAT |
| | WAS PERMITTED, NO STAIRWAY TO THE CHOIR LOFT. |
| | THIS REVISION # 2 SHEETS A5.1 AND A-7.1 AND OTHER |
| | SHEETS SHOW A NEW SPIRAL STAIRWAY FROM THE BASEMENT |
| | LEVEL, TO FIRST FLOOR AND TO THE CHOIR LOFT. NEITHER |
| | LIFE SAFETY SHEET A.3.3 LIFE SAFETY SHEET BASEMENT NOR |
| | A3.4 THE FIRST FLOOR LIFE SAFETY SHEET SHOW THE SPIRAL |
| | STAIR PART OF THE LIFE SAFETY PLAN. |
| | |
| | 4A) THE DOORS LEADING THE STAIRWAY VERTICAL SHAFT DO |
| | NOT GIVE ANY SIZE NOR FIRE RATING. 2017 FBC-B 1010.1.1 |
| | AND TABLE 716.5 OPENING PROTECTIVES. |
| | |
| | 4B) THE COVERSHEET NOR ANY LIFE SAFETY SHEET GIVE THE |
| | OCCUPANT LOAD OF THE CHOIR LOFT, THIS IS NEEDED TO |
| | DETERMINE THE OCCUPANT LOAD TO USE THE STAIR TO THE |
| | CHOIR LOFT. 107.2.1.2. ADDITIONAL INFORMATION REQUIRED. |
| | PLEASE SHOW COMPLIANCE FOR 1011.10 SPIRAL STAIRWAY AND |
| | AN OCCUPANT LOAD OF NOT MORE THAN 5 OCCUPNTS. |
| | |
| | 4C) IF THE SPIRAL STAIRCASE CAN BE CONSIDERED A MEANS |
| | OF EGRESS PLEASE PROVIDE SHOP DRAWINGS IN COMPLIANCE |
| | WITH 1011. 10 & 1011.11. |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |